13.0 TROUBLESHOOTING

SYMPTOM

PROBLEM

TEST SOLUTION

Pilot will not 
light.

Makes noise 
with no 
spark at pilot 
burner.

Wiring.

 

-

Verify the “S” wire for the sensor and the “I” wire for the ignitor 
are connected to the terminals on the module and pilot assembly.

Loose connection.

 

-

Verify no loose connections, electrical shorts in the wiring or 
ground out to any metal object.

Module.

 

-

Turn the ON/OFF switch to the “OFF” position. Remove the 
igniter wire “I” from the module. Place the ON/OFF switch to 
the “ON” position. Hold a grounded wire about 3/16” away from 
the “I” terminal on the module. If no spark, the module must be 
replaced. If there is a spark, the module is 

fi

 ne. Inspect pilot 

assembly for a shorted wire or cracked insulator around the 
electrode.

Igniter Spark gap is 
incorrect.

 

-

Spark gap of the ignitor to the pilot should be .12” or 1/8”

Transformer.

 

-

Verify the transformer is installed and plugged into the relay 
box. Check voltage of the transformer under load at the spade 
connections on the relay box with the ON/OFF switch in the 
“ON” position. Acceptable readings of a good transformer are 
between 2.8 and 3.4 volts A.C.

A shorted or loose
Connection.

 

-

Remove and reinstall the wiring harness that plugs into the module. 
Remove and verify continuity of each wire in wiring harness.

Battery backup

 

-

Check batteries.

Improper switch 
wiring.

 

-

Troubleshoot the system with the simplest ON/OFF switch.

Pilot sparks 
but will not 
light.

Gas supply.

 

-

Verify that the incoming gas line ball valve is “Open”. Verify that the 
inlet pressure reading is within acceptable limits, inlet pressures 
must not exceed 13” W.C. (7” W.C. for NG and 13” W.C. for LP).

Out of propane gas.

 

-

Fill the tank.

Carbon 
is being 
deposited on 
glass, logs, 
rocks, media 
or combustion 
chamber 
surfaces.

Air shutter has 
become blocked.

 

-

Ensure air shutter opening is free of lint or other obstructions.

 

-

Ensure air shutter is properly set.

Flame is impinging 
on the glass, 
logs, rocks, media 
or combustion 
chamber.

 

-

Check that the glass, logs, rocks or media are correctly positioned. 

 

-

Open air shutter to increase the primary air.

 

-

Check the input rate: check the manifold pressure and ori

fi

 ce size 

as speci

fi

 ed by the rating plate.

 

-

Check that the door gasketing is not broken or missing and that 
the seal is tight.

 

-

Check that both vent liners are free of holes and well sealed at all 
joints.

 

-

Check that minimum rise per foot has been adhered to for any 
horizontal venting.

42.13A

!

WARNING

ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT, 

WITH THE GLASS DOOR OPEN OR REMOVED.

TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THE APPLIANCE.

APPLIANCE MAY BE HOT, DO NOT SERVICE UNTIL APPLIANCE HAS COOLED.

DO NOT USE ABRASIVE CLEANERS.

Содержание CHDX40NT

Страница 1: ...life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any e...

Страница 2: ...RMINAL INSTALLATION 21 4 3 MOBILE HOME 22 4 4 ACCESS PANEL FOR GAS LINE CONNECTION 22 4 5 GAS INSTALLATION 23 5 0 FRAMING 24 5 1 MINIMUM CLEARANCE TO COMBUSTIBLES 26 5 2 MINIMUM CLEARANCE TO COMBUSTIB...

Страница 3: ...IBLE ENCLOSURES section for drywall or other combustible material Framing see FRAMING section Side Wall Venting see VENTING section Framing see FRAMING section Enclosures see the section MINIMUM CLEAR...

Страница 4: ...or other materials in the appliance It is imperative that the control compartments burners and circulating blower and its passageway in the appliance and venting system are kept clean The appliance an...

Страница 5: ...ent sealed combustion product ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT WITH THE GLASS DOOR OPENED OR REMOVED PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPER...

Страница 6: ...volt D batteries not supplied are required for the battery pack included in the system Use Alkaline batteries only 2 3 GENERAL INFORMATION FOR YOUR SATISFACTION THIS APPLIANCE HAS BEEN TEST FIRED TO...

Страница 7: ...CELLERL VENT APR S AVOIR EFFECTU LE SERVICE DU SYST ME DE PRISE D AIR ELECTRICAL RATING CLASSIFICATION 115V 60HZ LESS THAN 12 AMPS SP CIFICATIONS LECTRIQUES 115 V 60 HZ MOINS DE 12 A APPAREIL DE CHAUF...

Страница 8: ...ELBOW TO ENSURE THIS GAP IS MAINTAINED THESE SPACERS MUST NOT BE REMOVED Use only Wolf Steel Simpson Dura Vent Selkirk Direct Temp American Metal Amerivent or Metal Fab venting components Minimum and...

Страница 9: ...nnections is two horizontally or three vertically excluding the appliance and the air terminal connections when using flexible venting Horizontal runs may have a 0 rise per foot however for optimum pe...

Страница 10: ...10 W415 0889 A 08 11 10 24 MIN 38 24 MAX 62 MIN PLUS RISE 16 MIN 40FT MAX 3FT MIN 38 3 2 TYPICAL VENT INSTALLATIONS See VENTING section...

Страница 11: ...l grading is completed the bottom air slot is located a minimum 12 above grade The maximum allowable vent length is 10 9 1 30 MIN 12 MIN TO GRADE 3 3 SPECIAL VENT INSTALLATIONS 3 3 1 PERISCOPE TERMINA...

Страница 12: ...8 Roof must be non combustible without openings Q 3 3 See chart for wider wall dimensions R 6 6 See chart for deeper wall dimensions The terminal shall not be installed on any wall that has an open i...

Страница 13: ...al rise equal to or greater than the horizontal run 3 times the vertical rise equal to or greater than the horizontal run 3 5 VENT APPLICATION FLOW CHART 14 1 For the following symbols used in the ven...

Страница 14: ...4 5 FT HO 03 three 90 elbows 90 03 270 90 5 4 FT HT HR HO 4 5 5 4 9 9 FT HT VT 9 9 11 20 9 FT Formula 1 HT VT 9 9 11 Formula 2 HT VT 40 FT 20 9 40 Since both formulas are met this vent configuration i...

Страница 15: ...7 6 16 7 FT Formula 1 HT 4 2 VT 4 2 VT 4 2 x 6 25 2 FT 10 7 25 2 Formula 2 HT VT 24 75 FT 16 7 24 75 Since both formulas are met this vent configuration is acceptable 0 5 15 20 100 50 150 12 5 24 57...

Страница 16: ...Formula 1 HT VT Formula 2 HT VT 40 feet Example 6 V1 5 FT V2 6 FT V3 10 FT VT V1 V2 V3 5 6 10 21 FT H1 8 FT H2 2 5 FT HR H1 H2 8 2 5 10 5 FT HO 03 four 90 elbows 90 03 360 90 8 1 FT HT HR HO 10 5 8 1...

Страница 17: ...3 2 1 1 5 4 5 FT H1 6 FT H2 2 FT HR H1 H2 6 2 8 FT HO 03 four 90 elbows 90 03 360 90 8 1 FT HT HR HO 8 8 1 16 1 FT HT VT 16 1 4 5 20 6 FT Formula 1 HT 3VT 3VT 3 x 4 5 13 5 FT 16 1 13 5 Since this form...

Страница 18: ...ON OF THE APPLIANCE FOLLOW THE VENTING INSTRUCTIONS EXACTLY ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED RTV HIGH TEMP SILICONE SEALANT W573 0002 NOT SUPPLIED OR...

Страница 19: ...order specific kits required A Determine the air terminal location cut and frame a square opening as illustrated in the ceiling and the roof to provide the minimum 1 clearance between the vent pipe a...

Страница 20: ...length needed for the finished wall surface Slip the vent pipe a minimum of 2 over the inner sleeve of the air terminal and secure with 3 8 screws Apply a heavy bead of the high temperature sealant W5...

Страница 21: ...connector showing above the top of the flashing Slide the flashing underneath the sides and upper edge of the shingles Ensure that the air terminal connector is properly centred within the flashing g...

Страница 22: ...4 diameter holes located in the front left and right corners of the base Use 10 hex head screws inserted through the holes in the base to secure For free standing products contact your local authorize...

Страница 23: ...ment for shifting the burner assembly on it s side to aid with servicing components Check for gas leaks by brushing on a soap and water solution WARNING RISK OF FIRE EXPLOSION OR ASPHYXIATION ENSURE T...

Страница 24: ...ME THIS WILL ENSURE THAT CLEARANCE TO COMBUSTIBLES IS MAINTAINED WITHIN THE CAVITY DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND OFFS FAILURE TO MAINTAIN AIR SPACE CLEARANCE MAY CAUSE OVER HEATI...

Страница 25: ...hing material thickness to maintain clearances DO NOT BUILD INTO THIS AREA IT MUST BE LEFT CLEAR TO PROVIDE ADEQUATE CLEARANCE FOR THE VENT IN THIS 14 WIDE AREA CENTERED ALONG THE FRONT OF THE APPLIAN...

Страница 26: ...equire a minimum clearance of 18 at the top of the vent pipe See MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES section Use firestop spacer W010 1800 supplied where vent pipe penetrates combustible walls...

Страница 27: ...iance must be left unobstructed It is recommended that the enclosure be ventilated at the top and bottom to circulate the hot air See VENTING section 84 46 38 9 1 2 NON COMBUSTIBLE MATERIAL 2 1 WOOD H...

Страница 28: ...thereof are suitable Materials that are reported as passing ASTM E 136 Standard Test Method for Behaviour of Materials in a Vertical Tube Furnace at 750 C and UL763 shall be considered non combustible...

Страница 29: ...RNING RISK OF FIRE MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO OVERHEAT ENSURE ALL CLEARANCES I E B...

Страница 30: ...ON AS ILLUSTRATED DO NOT STRIKE SLAM OR SCRATCH GLASS DO NOT OPERATE APPLIANCE WITH GLASS REMOVED CRACKED BROKEN OR SCRATCHED FACING AND OR FINISHING MATERIAL MUST NEVER OVERHANG INTO THE APPLIANCE OP...

Страница 31: ...NCTION PROPERLYAND DELAYED IGNITION MAY OCCUR THE LOGS ARE FRAGILE AND SHOULD BE HANDLED WITH CARE The individual logs can be easily identified by the numbers cast on the underside of each log PhazerT...

Страница 32: ...yed ignition PHAZERTM logs glow when exposed to direct flame Use only certified glowing embers and PHAZERTM logs available from your Authorized dealer 6 3 GLOWING EMBER PLACEMENT GLOWING EMBERS GLOWIN...

Страница 33: ...f the rear log support Ensure the clusters are sitting flat 6 5 4 Place the large notched rocks along the inside and outside edges of the rock support as desired 6 5 5 Place the remaining refractory r...

Страница 34: ...34 W415 0889 A 08 11 10 6 6 LOGO PLACEMENT Remove the backing of the logo sup plied and place on the glass view ing door or bottom access panel as illustrated 1 2 1 2 3 8 1 LOGO LOGO...

Страница 35: ...CTRICAL POWER BEFORE SERVICING THIS APPLIANCE USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE USING NON LISTED ACCESSORIES BLOWERS DOORS LOUVRES TRIMS GAS C...

Страница 36: ...must be taken to prevent drywall dust from coming into contact with the blower or its compartment Any damage resulting from this condition is not covered by the warranty policy To safely install the...

Страница 37: ...in the same wall box 8 1 3 Wire the appliance junction box to 110 VAC for proper operation of the appliance 8 1 4 Refer to WIRING DIAGRAM section 8 1 5 This appliance is equipped with an electronic co...

Страница 38: ...Connect the 120 volt supply wire to the receptacle as per the CSA C22 1 Canadian Electrical Code in Canada or the ANSI NFPA 70 1996 National Electrical Code in the United States 8 3 5 Once the wiring...

Страница 39: ...E THROUGH INDEPENDENT CONDUIT YELLO THROUGH GAS LINE CONDUIT RED BLACK NIGHT LIGHT 12 VOLT TRANSFORMER A wall switch must be installed in a convenient location for the burner operation The recommended...

Страница 40: ...tric switch do not use any phone in your building 1 Stop Read the above safety information on this label 2 Turn remote wall switch to off position 3 Turn off all electrical power to the appliance and...

Страница 41: ...ustment Chart These settings are for maximum horizontal termination Adjustment may be required depending on fuel type vent configuration and altitude VENTURI ADJUSTMENT CHART FUEL CHDX40 NG 3 16 LP 7...

Страница 42: ...y vacuuming or brushing at least once a year 3 Check to see that all burner ports are burning Clean out any of the ports which may not be burning or are not burning properly 4 Check to see that the pi...

Страница 43: ...ructions 11 1 1 Turn off all electrical supply 11 1 2 Remove the glass door see DOOR REMOVAL INSTALLATION section 11 1 3 Unscrew the lens cover and lift the lamp straight out Replace with Wolf Steel L...

Страница 44: ...OR SCRATCH GLASS DO NOT OPERATE APPLIANCE WITH GLASS REMOVED CRACKED BROKEN OR SCRATCHED 56 2 11 3 CARE OF GLASS 5 1 DO NOT CLEAN GLASS WHEN HOT DO NOT USE ABRASIVE CLEANERS TO CLEAN GLASS Buff lightl...

Страница 45: ...DESCRIPTION 1a W725 0032 DEXEN VALVE 3V NATURAL GAS 1b W725 0049 DEXEN VALVE 3V PROPANE 2a W100 0069 PILOT ASSEMBLY PSE NG 2b W100 0093 PILOT ASSEMBLY PSE LP 3 W720 0092 PILOT TUBE PSE 4a W455 0049 P...

Страница 46: ...DOORS 45 ANIH ANDIRONS 46 W660 0081 THERMOSTAT WALL MOUNT DIGITAL 47 F40 ON OFF HAND HELD REMOTE CONTROL 47 F40 6 ON OFF HAND HELD REMOTE CONTROL BULK OF 6 48 F50 ON OFF HAND HELD REMOTE CONTROL 48 F5...

Страница 47: ...REF PART NO DESCRIPTION 64 GD 410 1 12 TO 7 12 PITCH 65 GD 411 8 12 TO 12 12 PITCH 66 GD 412 FLAT ROOF 67 W490 0074 5 8 INNER OUTER SLEEVE 68 W670 0007 5 8 TERMINAL 69 W170 0086 STORM COLLAR 70 W010 0...

Страница 48: ...tinuity of each wire in wiring harness Battery backup Check batteries Improper switch wiring Troubleshoot the system with the simplest ON OFF switch Pilot sparks but will not light Gas supply Verify t...

Страница 49: ...that you have all wires connected and in the right order Module or valve Conduct the following test to verify if the problem is the module or valve To measure voltages turn the multimeter to DC place...

Страница 50: ...not in any event extend to any incidental consequential or indirect damages This warranty defines the obligations and liability of CONTINENTAL with respect to the CONTINENTAL gas heater and any other...

Страница 51: ...51 W415 0889 A 08 11 10 15 0 SERVICE HISTORY 43 1...

Страница 52: ...52 W415 0889 A 08 11 10 44 1 16 0 NOTES...

Отзывы: