41
W415-1516 / A / 10.22.15
EN
!
WARNING
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE
CLEARLY MAINTAINED.
WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL, THE PAINT OR LACQUER MUST BE
HEAT RESISTANT TO PREVENT DISCOLOURATION.
73.1
6.6 MINIMUM MANTEL CLEARANCES
Position the remote receiver in the valve compartment close to the electrical junction box. Ensure the
receiver is on top of the placement label, if equipped.
35.25
PLACE REMOTE
RECEIVER ON TOP
OF THIS LABEL
FIREPLACE BASE
JUNCTION
BOX
6.7 REMOTE RECEIVER PLACEMENT
TOP OF FRONT
OPENING
8" (203mm) MANTLE
6" (152mm) MANTLE
4" (102mm) MANTLE
2" (51mm) MANTLE
12"
(305mm)
18"
(457mm)
16"
(406mm)
14"
(356mm)
0
$
1
7
/
(
+
(
,
*
+
7
2
4
6
8 10 12
MANTLE DEPTH (")
12
14
16
18
20
22
(")
Combustible mantel clearance can vary according to the mantel depth.
Use the graph to help evaluate the clearance needed.