52
BATTERY light is
yellow
Battery test in progress
Wait until the battery test is
finished. If the batteries are
connected by software, the light
is green.
FAN light is red
Fan failure, the fan does not
spin.
Fault reset - "RESET" button. If
the solution does not help,
contact the
supplier/manufacturer. Service is
required.
FAN light is organge
Insufficient fan speed,
reduced power.
Fault reset - "RESET" button. If
the solution does not help,
contact the
supplier/manufacturer. Service is
required.
Extinguishing level
indicator signals
empty
Fire
extinguisher
leak
caused by extinguishing, by
a rise in temperature or by
an increase in pressure in
the tank. Fire extinguisher
is leaking through the
safety valve.
Contact the
supplier/manufacturer. Service is
required.
Содержание LES-RACK