26
IP address: device IP-address.
Gateway: must be entered even if not used.
Primary and secondary DNS: in case of mail functions use.
SNMP trap1, 2:
IP: SNMP-server address.
Port: default value is 162, can be edited, if the port is occupied.
Community: SMNP trap community.
TCP port: TCP communication port.
UDP port: UDP communication port.
Read, Write community: SNMP community.
Refresh HTML: window content refresh rate in ms.
Type: Title
Header: header text.
Footer: footer text (HTML tags can be used to link to web addresses).
Group extinguish: the devices entered to the same group (except 0) will be activated
simultaneously, if a fire is detected by any of them. Same works with testing, muting, and
resetting after the extinguishing. The devices should be in the same network segment. For
other cases UDP broadcasting can be used.
BAUD RATE: RS485 speed (2400, 4800, 9600, 19200)
Modbus ID: slave ID
User, Password: editing username and password.
NOTE: If the IP address or password is forgotten or lost, they can be reset to default
values
For that, press and hold down the “RESET” button until the LED indicator starts
flashing green and red, now you have several options:
Press the TEST button, and the device will default password and IP address
values.
Press the MUTE button, and the device will reset without changing its settings.
Press the RESET button to exit reset mode.