49
○
Installation and commissioning checklist
The temperature indicator has not exceeded the permitted limit
The device was inserted horizontally (checked with a level meter)
The power cord is plugged into the power port AC power cord (12)
The temperature cable is inserted into the RJ11 port
The device is undamaged and shows no defects from improper handling
The nozzle is pointing downwards and shows no signs of damage
On the signaling panel - SYSTEM READY lights up intermittently in green
The battery is connected - BATTERY lights up green
On the signaling panel - FAN lights up green
All other controls on the signaling panel are off
Software control of fire extinguisher level
In the case of connecting external peripherals:
Sounder LED Beacon
physically connected to the device with the correct connection of resistors
software set notifications in case of fault
Manual release extinguishing button
physically connected to the device with the correct connection of resistors
software set to activate extinguishing
software set notifications in case of fault
Door sensor switch
physically connected to the device with the correct connection of resistors
software set to block extinguishing when the door is open
software set notifications in case of fault
the Extinguishing light does not flash red
the Extinguishing light flashes red when the door is opened
Temperature monitoring sensor
physically connected to the device with the correct connection of resistors
activated via software
The FAULT: SYSTEM light does not flash red
On the signaling panel - SYSTEM READY lights up intermittently in green
The battery is connected - BATTERY lights up green
On the signaling panel - FAN lights up green
All other controls on the signaling panel are off
Software control of fire extinguisher level
Serial number:
Date: