35
LED Beacon
Battery
13
Disconnected
Connected
63
Failure
External sensor 1
14
OK
Active
64
Failure
External sensor 2
15
OK
Active
65
Failure
External sensor 3
16
OK
Active
66
Failure
Gas Valve
17
Closed
Open
67
Failure
Extinguishant Valve 18
Closed
Open
68
Failure
Extinguishant level
19
OK
Low
69
Failure
Power Supply230V
AC
20
OK
Outage
70
Power Supply 24 V
DC
21
OK
Battery test
71
Failure
Power Supply 12 V
22
72
Failure
Power Supply 29 V
23
73
Failure
Temperature 1 -
internal
24
OK
Temperature exceeded
set limit
74
Failure
Temperature 2 -
external
25
OK
Temperature exceeded
set limit
75
Failure
Temperature 3 -
external
26
OK
Temperature exceeded
set limit
76
Failure
Fan
27
Idle
OK
77
Failure
28
78
Mute
29
Alarm inactive
79
Test
30
Testing
80
Reset
31
Resetting
81
Minor
32
Active
82
Major
33
Active
83
Blocking
34
Extinguishing blocked 84
Extinguishing
35
Activated
85
System Alarm
36
86
System
Failure
Function 4 - read inputs
Reg.0..4
0 – Temperature 1- internal – 1 decimal
1 – Temperature 2 – external – 1 decimal
2 - Temperature 3 – external – 1 decimal
3 – power voltage - 2 decimals
4 – level sensor value – 0-100%, values above 100 indicates failure
Function 5 – write single coil.
Reg. 0-3 activates output relays.