TD SOLUS II:
Connection with boiler buffering
7
La
st
r
ev
is
ed
0
5/
20
0
9
3.3
System diagram with solar power system and
hot water circuit
Solar-Aus
Collector
Underfloor
heating
HP
M
Pz
Sup
Ret
Boiler
Solar cold
Solar hot
Ps
HS
R1/2
R3
BS 2
CW
HW
Connection for heat pumps and generally for optimised
solar yield:
Solar-Aus
Collector
Underfloor
heating
Ph
M
Pz
Sup
Ret
Heat pump/
Boiler
Solar cold
Solar hot
Ps
HS
R1/2
R3
BS 2
BS 1
CW
WW
U1
U2
Hot water backup heating: U1 and U2 up.
Heating operation: U1 and U2 down.
Circulation switching version for thermal disinfection of the
circulation line:
Pz
CW
3.4
Connection assignment for boiler and heating
circuit
3.4.1
One boiler, one heating circuit
See also diagram 0 on page 12.
Heating
Circuit
70/50
60/40
Sup
Ret
Boiler
HS
BS
>30°C R1
<30°C R3
Example 1:Heating circuit 70/50 to 60/40
Heating
Circuit
70/50
60/40
Sup
Ret
Wood-fired
boiler
HS
BS
>30°C R1/2
<30°C R3
Example 2: Solid fuel boiler
For solid fuel boilers (e.g. firewood), the boiler return is
connected to R3 to utilise the entire storage tank capacity. If
the heating circuit return is also connected to R3, the full
capacity is available for heating purposes. However, there
may be higher temperatures in the bottom of the storage
tank, which decreases the
solar utilisation.