background image

TD SOLUS II: 

Installation

 

 

 

 

 

16 

 

La

st

 r

ev

is

ed

 0

5/

20

0

9

  

 

Component designations: 

1.

 

Shut-off valve 

2.

 

Pressure-reducing valve (if the 
network pressure is greater than 
8 bar and there is no pressure-
reducing valve at the building 
connection) 

3.

 

Test valve 

4.

 

Non-return valve  

5.

 

Manometer connection with 
manometer 

6.

 

Shut-off valve 

7.

 

Safety valve 

8.

 

Drain funnel 

9.

 

Drainage valve 

10.

 

Sanitary expansion vessel, e.g. 
water-shock damper 

11.

 

Thermostatic hot water mixer 

Safety valve (7):  

 

No dirt traps or other constrictions may be fitted in the 
supply pipe. 

 

Close at a pressure drop of 20 % of the response pres-
sure.  

 

To be installed in an easily acessible location, so that it 
can be opened during operation. A warning notice with 
the following text must be displayed at the safety valve 
or at its blow-off line: "For safety reasons, water may 
escape from the blow-off line during heating! Do not 
close".  

 

Install appropriately to ensure that no-one is endan-
gered by hot water or steam from the valve.  

Blow-off line:  

 

The minimum size is the diameter of the safety valve 
outlet 

 

Max. 2 bends, 2 m in length 

 

Max. 3 bends, 4 m length possible if one size larger.   

 

Laying with gradients 

 

The drain pipe downstream of the drain funnel must 
have at least twice the diameter of the valve. 

Water-shock damper:  

Thermal expansion of the hot water in the heat exchanger 
causes water loss through the safety valve. Optional rem-
edy: Mount water-shock damper downstream of the non-
return valve or at any point in the hot water pipe. 

Non-return valve (4): 

The requirements pertaining to the fitting of a non-return 
valve, and its design (approval), are contained in DIN 
1988 and DVGW worksheet W 376.  

Pressure reducing valve (2): 

In accordance with DIN 3320, a system operating pres-
sure should be assigned to the permitted operating over-
pressure of the hot water heat exchanger. If the pressure in 
the cold water supply pipe leading to the solar storage 
tank is over 8 bar, a pressure reducer (which has been 
tested and approved as compliant with DVGW worksheet 
W 375) must be installed to reduce the cold water pres-
sure to max. 8 bar. If mixer taps are used, a centralised 
pressure reducer must be fitted. 

Drainage valve (9): 

Water heating systems must be fitted with a device (usually 
at the cold water connection) which facilitates draining the 
system as completely as possible without dismantling. 

Fine filter: 

If the water quality is poor or if the pipelines are old, a 
fine filter must be installed upstream of the storage tank 
inlet. 

Deliming method 

If the water hardness is 8° dH or more, rinsing taps are 
recommended for the cold water inlet and the hot water 
outlet. For use with water high in limescale, limescale ex-
perts recommend limescale conversion or water treatment 
processes for all solar heating systems with 14° dH and 
upwards (hard water). You can ask your local water sup-
ply company to find out the water hardness. Ask your in-
staller for advice on this matter. 

Circulation line: 

Connect the circulation line to the cold water connection of 
the storage tank and fit a check valve to prevent short cir-
cuit flows of cold water into the hot water network. Oper-
ate the circulation pump for short periods only (minutes) to 
prevent high heat losses and a gradual mixing of the stor-
age tank. CONTROL units provide suitable switching func-
tions for this. 

8.5.4

 

Thermostatic hot water mixer (11) 

A thermostatic hot water mixer must be installed to restrict 
the maximum hot water temperature, as there is no tem-
perature limiter fitted in the storage tank.  

8.5.5

 

Electric heating rod 

To install an electric heating rod, break out the pre-drilled 
hole in the PS insulating shell and use a sharp knife (spray 
the cutting surface with silicone grease) to cut the EPS insu-
lation along the edge of the drilled hole.  
After the electric heating rod has been installed, close the 
hole with the cover provided for this purpose (delivered 
with the electric heating rod). 

Содержание SOLUS II 1000

Страница 1: ...OMBINED STORAGE TANK 2 1 1 Special advantages 2 2 PLANNING AID 4 2 1 Transport 4 2 2 Connection to the drinking water supply 4 2 3 Connection to the solar power system 5 2 4 Connection to the boiler and heating circuit 5 2 5 Parallel connection of two SOLUS II storage tanks 5 2 6 Electrical backup heating 5 2 7 Materials 5 2 8 Standards 6 2 9 Return acceptance statement 6 3 CONNECTION WITH BOILER ...

Страница 2: ...efore they are even suitable for apartment buildings or the temperature of the hot water stand by volume can be kept to a minimum This facilitates increased solar utilisa tion and is a requirement for operation with heat pumps Heat loss is minimised via the aluminium reflector in the cylinder and the PP inserts for practically complete pre vention of microcirculation losses via the storage tank co...

Страница 3: ...d water inlet circulation Heating boiler return R3 e g wood boiler The heat exchangers are particularly effective and rely on the counterflow princi ple Efficient storage tank management via optimised control using CONTROL series 560 L and 850 L Top cold water connection COMFORT Line SOLUS II 550 800 1000 Flow arrows EPS insulation in the lid area especially thick Hygienic hot water via hot water ...

Страница 4: ...torage tank As in all water heaters hot water circulation entails significant heat losses This also gradually reduces stratification The circulation pump should not run continuously as otherwise unnecessarily high heat losses result in the piping system For this reason we recommend operating the circulation pump with temperature control or in interval mode most CONTROL controllers contain this fun...

Страница 5: ...d for low return temperatures When using boilers which are sensitive to low return tem peratures appropriate precautions must be taken espe cially when connection R3 is used The target temperature for the hot water standby portion set on the boiler or solar controller must be approx 10 15 K greater than the hot water temperature actually required depending on the tap output required The boiler sup...

Страница 6: ...t supply temperatures are lower than the hot water standby temperature Even great boiler outputs are buffered This facilitates longer runtimes and standstill times with low emissions Even in modulating boilers buffering may be beneficial for the non modulating partial load range The boiler can cool down during standstill 3 2 Connection rules The heating circuit supply is generally fitted to the co...

Страница 7: ...rsion for thermal disinfection of the circulation line Pz CW 3 4 Connection assignment for boiler and heating circuit 3 4 1 One boiler one heating circuit See also diagram 0 on page 12 Heating Circuit 70 50 60 40 Sup Ret Boiler HS BS 30 C R1 30 C R3 Example 1 Heating circuit 70 50 to 60 40 Heating Circuit 70 50 60 40 Sup Ret Wood fired boiler HS BS 30 C R1 2 30 C R3 Example 2 Solid fuel boiler For...

Страница 8: ...s for a boiler without a solid fuel boiler see section 3 4 1 3 4 4 Increased hot water requirement If a volume greater than the maximum hot water standby volume is required the heating supply can be connected to R1 The hot water sensor is then inserted into sensor sleeve FH D small buffer bottom 3 4 5 Instantaneous water heaters with integrated switching valve or with two integrated pumps The hot ...

Страница 9: ...ure Return connection 40 C R1 30 C R3 Table 5 4 2 1 Return increase with boiler See also diagram 0 on page 12 Instantaneous water heater HS 30 C R1 2 30 C R3 BS HW Heating Circuit 50 35 Example 6 Heating circuit 50 35 4 2 2 Instantaneous water heaters with integrated switch ing valve or with two integrated pumps With instantaneous water heaters with integrated valve or second integrated pump for s...

Страница 10: ...Double capacity for hot water and solar heat exchangers for two SOLUS II storage tanks 5 1 Advantages limits Simple expansion of the storage tank capacity via parallel connection with a buffer storage tank Greater storage tank volume possible even with restricted access conditions Retrofitted connection possible 5 2 Connection rules 5 2 1 Parallel connection of two SOLUS II storage tanks 2nd stora...

Страница 11: ...hot Solar cold SOLUS SOLUS Example 12 Connections for water and the solar power system 1 On the SOLUS II 1050 L and SOLUS II 2200 L the cold water con nection is under the solar cold connection 5 4 Connection example for cascade connection For solid fuel boilers the buffer volume can be increased with a buffer module by cascade connection of a SOLUS The buffer module is charged by the solid fuel b...

Страница 12: ...02 3602 kvs m3 h 1 28 1 1 1 28 1 1 1 28 1 0 1 0 Max permissible temperature C 90 90 90 90 Max permissible operating pres sure bar 8 8 8 8 1 Significantly better performance than conventional heat exchangers due to chimney effect with equal surface area 2 10 l min 3 at 15 l min Thermal insulation Unit 550 560 L NFL 800 850 L 1000 1050 L 2200 L Material EPS ALU EPS 1 EPS ALU EPS 1 EPS ALU EPS 1 ALU ...

Страница 13: ...ter and circulation connection on the SOLUS II 1050 L and SOLUS II 2200 L are under the solar cold connection Connection BS1 is 15 mm long and intended for parallel con nection with a buffer module Connections Sensor sleeves Unit 550 560L NFL 800 850L S PM 1000 S PM 1050L 2200L Suitable for 6 mm sensor Venting valve and hose Sensor sleeve A hot wa ter small mm 1245 1535 1560 1425 1425 Storage tank...

Страница 14: ... LS ready mixed which can be pur chased from Consolar The antifreeze must be checked regularly in accordance with the regulations see also the technical documentation for CON SOLARSTATION and Acceptance and maintenance protocol 8 1 4 Pipe insulation The insulation of the pipelines has a major influence on the energy savings which can be achieved with the solar power system It is therefore recommen...

Страница 15: ... filter on the heating circuit re turn 8 5 2 Solar circuit Do not connect the solar circuit and operate the solar pump until the storage tank has been filled Recommendation Smoothing section at the lowest point of the solar circuit supply so that corrosion products caused by oxygen leaks are deposited there 8 5 3 Cold and hot water connection Make all connections in accordance with the respective ...

Страница 16: ...d water supply pipe leading to the solar storage tank is over 8 bar a pressure reducer which has been tested and approved as compliant with DVGW worksheet W 375 must be installed to reduce the cold water pres sure to max 8 bar If mixer taps are used a centralised pressure reducer must be fitted Drainage valve 9 Water heating systems must be fitted with a device usually at the cold water connection...

Страница 17: ...e clamp screw fitting Tighten the union nut by hand and then one more turn using a spanner or 3 4 of a turn for 22 mm 8 6 Filling Flush the water and heating circuits Fill the storage tank open the venting valve while you do so A small quantity of water may escape from the inner piping before the air escapes Fill the water and heating circuits Vent the heating circuits While doing so run the corre...

Страница 18: ...t 11 6 foam plugs for sensor holes 35 12 8 plastic clips installation aid 13 Hose with venting valve CW Cold water circulation HW Hot water S1 Solar input S2 Solar output BS1 boiler supply top BS2 boiler supply HS heating supply R1_2 return 45 C R3 return 35 C SS A E Sensor sleeve Before fitting the side parts Attach the three enclosed long foam strips 7 with self adhesive tape to the storage tank...

Страница 19: ... and the floor again and adjust using the feet 3 4 Clip the plastic clips to secure the terminal strip con nection Connect the other sides of the side insulation to one an other and secure them using the plastic clips to make in stallation easier Check Side parts without offset at the top So that the insulating foam lid can subsequently be fitted without gaps Latch the strip of hooks into the firs...

Страница 20: ...t the sensor installation aid IMPORTANT The sensors must be pushed in as far as possible Seal the holes care fully with the foam plugs for sensors 35 Screw the sensor cover over the openings Connect the temperature sensors to the controller in ac cordance with the operating instructions of the corre sponding controller Route the sensor cables and 230 V cables in separate or partitioned cable condu...

Страница 21: ... heating of the hot water stor age tank if no expansion vessel is installed The blow off line must be open at all times 9 2 2 Holiday For extended breaks in usage during the summer Preserve the solar collectors and storage tanks Set the storage tank cooling function from 70 C on the control ler Save pump energy Remove the insulation lid 9 2 3 Deliming the hot water heat exchanger No limescale is b...

Страница 22: ...re all connected pipes solar boiler cold and hot water at ambient temperature during standstilll If not please ask your installer to conduct testing and if necessary installation of non return valves Is the insulation in close contact with the floor If not seal the gap If despite all of these measures the hot water tempera tures in the technical data of the SOLUS II cannot be achieved please call ...

Отзывы: