16
4.3
Electrical connection
4.3.1
Necessary qualification of the assembly personnel
4.3.2
Establishing the electrical connections
The internal system modules are already wired to the control unit upon delivery.
The power supply to the control unit is provided by the cable that is permanently
connected to the control unit with the integrated 230V-50Hz/ 12V-50Hz AC-AC adapter.
The control unit’s current consumption with the system‘s connected internal actuators is
500 mA.
An AC earthed socket (type CEE 7/3) fused in accordance with the system output must be
assembled within reach of the control unit connection cable’s length. Then, insert the plug
of the control unit’s power supply cable into the socket.
One output each is available on the control unit for the signalling of a regeneration (RLY1)
and of an internal control error (RLY2) to the ZLT, (labelled RLY1 and RLY2 respectively
at the right edge of the board).
Installation and assembly
DANGER!
The electrical installation must be carried out by a qualified electrician, in compliance with the
VDE and EVU installation regulations, factory standard, etc. and in accordance with the valid
country-specific regulations.
DANGER!
The electrical installation must be carried out by a qualified electrician, in compliance with the
VDE and EVU installation regulations, factory standard, etc. and in accordance with the valid
country-specific regulations.
This involves two live NO contacts with a joint 12VDC conductor (COM), with an authorised
load of 100mA per output. The total current of both outputs must not exceed 200mA.
If potential-free signal outputs are required, the on-site installation of two cut-off relays
with 12 VDC/max. 100 mA is recommended. Check the installation dimensions of the
relays before assembling them under the control cover.
Содержание CONDAIR SOFT
Страница 31: ...31 Appendix 9 3 Electrical connection...
Страница 48: ...48 9 5 1 Soft 60 System drawing Appendix...
Страница 49: ...49 9 5 2 Soft 120 System drawing Appendix...
Страница 50: ...50 9 5 3 Soft 200 System drawing Appendix...
Страница 51: ...51 9 5 4 Soft 320 System drawing Appendix...
Страница 52: ...52 9 5 5 Soft 400 System drawing Appendix...
Страница 54: ...54 Notes...
Страница 55: ...55 Notes...