- 26 -
- wait 15 seconds until the thermostat display returns to the main screen,
or
- scroll through the settings by pressing the
button.
The setting options are shown in the table below:
Display
Function
Setting Options
Default Setting
Detailed Description
DIF
Selecting switching sensitivity
0.1 - 1.0 °C
0.2 °C
Chapter 11.1
SVH
Defining maximum settable temperature
5 – 99 °C
35 °C
----
SVL
Defining minimum settable temperature
5 – 99 °C
5 °C
----
ADJ
Calibration of the temperature sensor
-5 – +5 °C
0 °C
Chapter 11.2
FRE
Antifreezing
00: OFF
00
Chapter 11.3
01: ON
PON
Memorizing ON/OFF status in case of a
power failture
00: OFF
01
Chapter 11.4
01: ON
LOC
Setting the keylock funcion
01: only On/Off button works
02: all buttons locked
02
----
FUN
Changing between heating or cooling
mode
00: heating
01: cooling
00
Chapter 11.5.
SNP
Synchronization with a receiver unit
00: disable synchronization
01: enable synchronization
00
Chapter 7.3.
FAC
Resetting to factory default
00: Resetting to factory default
08: Saving settings
08
Chapter 11.6