The main parameters of the compressor are displayed after 5 seconds:
21°C
0.00HZ
0.0BAR
0RPM
STOP
C01
LOKAL
Main menu: Click
in order to bring up the options menu:
RUN PARAMETERS
USAGE PARAM
FACTORY PARAM
Includes current values (available for viewing)
Includes operating settings of the main parameters (available for viewing,
changes password-protected)
For servicing mode (view with password). Modification only possible by manufacturer
ADJUST. PARAM
Basic settings and maintenance hour counter (Password protected)
Description of the parameters. Run parameters:
Select the run parameters using the up
and down
buttons and enter
. Current values
are displayed.
M1 AND FAN CUR
TOTAL RUN TIME
THIS RUN TIME
MAINTEN. PARAM
ERRORS HISTORY
SERIAL NUMBER
THIS ERROR
COM. STATUS
The other menus have a similar structure.
Select the line
“
M1 AND FAN CUR
”
and press
.
M1(A) AND FAN(A)
Phase current of main motor and fan motor
A: 000.0 000.0
B: 0.0
0.0
C:0.0
0.0
TOTAL RUN TIME
TOTAL RUN TIME:
Total running hours (main engine running).
TOTAL LOAD TIME:
Total operating time under load (main engine suction valve open).
THIS RUN TIM
THIS RUN TIME:
The current operating time from the last start.
THIS LOAD TIME:
Current running time under load