Chapter 3. Configuring the Storage Cabinet
EK–SMCPR–UG. A01
387404–001
3–3
Table 3–1 EMU Set Point Temperature Conversions
°C
°F
°C
°F
°C
°F
ºC
°F
°C
°F
0
32
10
50
20
68
30
86
40
104
1
34
11
52
21
70
31
88
41
106
2
36
12
54
22
72
32
90
42
108
3
37
13
55
23
73
33
91
43
109
4
39
14
57
24
75
34
93
44
111
5
41
15
59
25
77
35
95
45
113
6
43
16
61
26
79
36
97
46
115
7
45
17
63
27
81
37
99
47
117
8
46
18
64
28
82
38
100
48
118
9
48
19
66
29
84
39
102
49
120
Table 3–2 Temperature Set Point Rules – EMU Firmware Vers. 1.0 and 1.1
1. Enter all temperatures in degrees Celsius (°C). Do not use fractions, decimals, or
degrees Fahrenheit (°F).
2. The EMU set point (sensor_3) temperature must be a minimum of 6°C (11°F)
greater than the highest expected ambient (intake) temperature.
3. The backplane set points (sensor_1 and sensor_2) must be the same temperature
and a minimum of 13
°
C (23
°
F) greater than the highest expected ambient
temperature. This requires a minimum setting of 7
°
C (13
°
F) greater than the EMU
set point.
4. EMU firmware versions 1.0 or 1.1
cannot use the
set emu
sensor_n_setpoint=default
command. Instead, the following command is
required:
set emu sensor_n_setpoint=nn
((where nn is the desired temperature in
°
C).