Guide:
SYSTIMAX
®
iPatch
®
Panel Manager Guide
4–14
Testing Panels
To test that the LEDs, port sensors, and buttons work on an iPatch Panel, iPatch
Fiber Shelf, or iPatch Fiber Module, perform the steps below.
1
At the iPatch Manager display, press any button to turn on the lighting. From
the Ready screen, press Menu.
2
Press
Ê
until the iPatch Manager display shows:
3
With Test Panels highlighted, press Select.
The iPatch Manager sounds a key beep and the display shows:
Note:
If a patch cord is inserted in any iPatch Panel port in the equipment room,
the iPatch Manager automatically exits the test mode.
4
Press any button on the panel or module that you want to test.
The iPatch Manager sounds a key beep.
Each LED on the panel or module sequentially turns on and off. The LED test
pattern repeats until you press a button on the panel or module, you press a
button on another panel or module, you press Exit, or until the test mode times
out. The display shows:
Note:
You can repeat this step to test each panel and module in the rack.
5
To test a port sensor and button on the panel or module, press the button
corresponding to the port that you want to test.
If the button is working
, the iPatch Manager sounds a key beep.
If no patch cord is connected to the port
, the LED blinks.
If a patch cord is
connected to the port
, the LED turns on.
Note:
You can repeat this step to test each of the port sensors or buttons on
the panel or module.
Run Diagnostics
Rack Information
Test Panels
Reset Panels
Reset Racks
Highlight a command. Then press Select.
Select Exit
Select a Panel to Test
Press any button on the panel.
Exit
Testing Panel 1
Rack: 08ACFB05 Panel: AD783D2F9232
To test a port, press its button.
Exit