Securing the Cable:
To secure the incoming fiber optic cable to the back of the shelf and rack:
1. Insert a flat cable tie holder (provided) up through the hole in the cable support on the rear of the shelf
on the side opposite from where the cable enters the shelf (Figure 12). For example, if the cable enters
the shelf on the right side, use the hole on the left side of the cable support.
2. Insert a cable tie (provided) through the cable tie holder and retain the incoming fiber optic cable to the
cable support.
Important:
Do not tighten the cable tie completely. Leave enough slack so that the cable moves freely
when you slide the shelf out from the rack.
3. Secure the incoming fiber optic cable to the back of the rack approximately 7 inches (about 18cm)
above the shelf (Figure 12).
4. Slide the shelf out of the rack and back in, making sure that it slides freely and the panel bus jumper
does not bind.
Note:
The ribbon cable of the panel bus jumper may slide in the corrugated tubing.
Figure 12 Securing the Cable to the Back of the Shelf and Rack
Panel bus jumper
Cable tie through cable tie retainer
Cable tie
Fiber optic cable