background image

5

PRODUCT DESIGN

Alcove Illustration

REAR

S

ID

E

S

ID

E

ALCOVE

24" at front is required for servicing or cleaning.

Note: 

In all cases accessibility clearance shall take

precedence over clearances from the enclosure where
accessibility clearances are greater.  All dimensions are
given in inches.

High Altitude Derate

When this furnace is installed at high altitude, the appropri-
ate High Altitude orifice kit must be installed. This is re-
quired due to the natural reduction in the density of both the
gas fuel and combustion air as altitude increases. The kit
will provide the proper design certified input rate within the
specified altitude range.

High altitude kits are purchased according to the installa-
tion altitude and usage of either natural or propane gas. Refer
to the chart above for a tabular listing of appropriate altitude
ranges and corresponding manufacturer’s high altitude Natu-
ral Gas and Propane Gas kits. For a tabular listing of appro-
priate altitude ranges and corresponding manufacturer's High
Altitude Pressure Switch kits, refer to either the 

Pressure

Switch Trip Points & Usage Chart

 in this manual or the 

Ac-

cessory Charts

 in Service Instructions.

2000

3000

4000

4500

5000

6000

7000

8000

US BURNER

ORIFICE

44/55

44/55

45/56

45/56

46/57

47/58

47/58

CANADA BURNER

ORIFICE

44/55

47/57

HA-02 HIGH ALTITUDE CONVERSION KIT REQUIRED

Tabled data is based upon the furnace input being reduced for altitudes above sea level.  U.S. 4% per 1,000 feet.

Canada 10% derate for 2,000-4,000 feet.

ELEVATION ABOVE SEA-LEVEL (FEET)

INPUT PER BURNER   -   22,500 BTUH NATURAL GAS / 20,000 BTUH L.P.

Single Stage Thermostat

A single-stage thermostat with only one heating stage may
be used to control this furnace.  The application of a single-
stage thermostat does not offer “true” thermostat-driven two-
stage operation, but provides a 

timed

 transition from low to

high fire.  The furnace will run on low stage for a fixed period
of time before stepping up to high stage to satisfy the
thermostat’s call for heat.  The delay period prior to stepping
up can be set at either a fixed 5 minute time delay or a load
based variable time between 1 and 12 minutes (AUTO mode).
If the AUTOmode is selected, the control averages the cycle
times of the previous three cycles and uses the average to
determine the time to transition from low stage to high stage.

To use a single-stage thermostat, turn off power to the fur-
nace, move the thermostat selection DIP switch to the OFF
position. Set the desired transition time by setting the tran-
sition delay DIP switch to the desired ON/OFF position. Turn
power back on. Refer to the following figure.

3

4

Thermostat

Stage Delay

Move to the ON position
to select two-stage
thermostat or OFF to
select single stage
thermostat

Move to the ON position
to select Auto transition
delay or OFF for 5 minute
transition delay

Heat OFF Delay
DIP Switches

ON

OFF

S1

Содержание ADVC8

Страница 1: ...to improper service procedures performed by an unqualified person ADVC8 AMVC8 GMVC8 80 Gas Furnace Units Refer to Service Manual RS6200004 for installation operation and troubleshooting information Al...

Страница 2: ...ge personal injury or death Goodman will not be responsible for any injury or property damage arising from improper service or service procedures If you install or perform service on this unit you ass...

Страница 3: ...uld questions arise contact your local EPA office WARNING WARNING Do not connect or use any device that is not design certified by Goodman for use with this unit Serious property damage personal injur...

Страница 4: ...ower door is not in place Keep the blower access doors in place except for inspection and maintenance These furnaces are also equipped with a self diagnosing elec tronic control module In the event a...

Страница 5: ...ONVERSIONKITREQUIR ED Tableddataisbaseduponthefurnaceinputbeingreducedforaltitudesabovesealevel U S 4 per1 000feet Canada10 deratefor2 000 4 000feet ELEVA TIONA BOVESEA LEVEL FEET INPUTPERBURN ER 22 5...

Страница 6: ...Door Interlock Switch Transformer Circulator Blower 1 2 3 4 5 6 7 8 9 Inductor 1 Tubular Heat Exchanger 2 Pressure Switch 3 Flue Pipe Connection 4 Induced Draft Blower 5 Gas Line Entrance 6 Gas Valve...

Страница 7: ...r Blower Inductor Pressure Switch 2 Gas Line Entrance Alternate Tubular Heat Exchanger 1 1 Tubular Heat Exchanger 2 Pressure Switch 3 Flue Pipe Connection 4 Induced Draft Blower 5 Gas Line Entrance 6...

Страница 8: ...8_____X Alt Gas Inlet High Voltage Inlet Low Voltage Alt Gas Inlet Alt High Voltage Alt LowVoltage MODELS A B AMVC80704BX GMVC80704BX 17 1 2 16 AMVC80905CX AMVC81155CX GMVC80905CX GMVC81155CX 21 19 1...

Страница 9: ...S 33 3 8 A B 28 High Voltage Electrical Low Voltage Electrical Gas Inlet MODEL A B NON COMBUSTIBLE FLOOR BASE ADVC80703BX 17 1 2 16 SBT17 ADVC80905CX ADVC81155CX 21 19 1 2 SBT21 All dimensions are in...

Страница 10: ...0 3 B X 1 A D V C 8 0 9 0 5 C X 1 A D V C 8 1 1 5 5 C X 1 A U X I L I A R Y L I M I T S W I T C H E S MODEL TRIP POINT ID BLOWER PRESSURE SWITCH LOW STAGE TRIP POINT ID BLOWER PRESSURE SWITCH HIGH STA...

Страница 11: ...CAUF equivalent All CHPF coils in B C D heights have an insulated Z bracket for use with one size smaller furnace All proper coil combinations are subject to being ARI rated with a matched outdoor un...

Страница 12: ...mine filter area requirement NOTE Filters can also be installed elsewhere in the duct system such as a central return FURNACE INPUT FILTER SIZE TYPE 45M 160 in2 permanent 70M 241 in2 permanent 90M 320...

Страница 13: ...owing downflow top return filter sizes depending on cabinet size Refer to Minimum Filter Area tables to determine filter area requirement NOTE Filters can also be installed elsewhere in the duct syste...

Страница 14: ...ted External Static w c 10 50 10 50 10 50 Temperature Rise F 20 50 20 50 25 55 High Stage Pressure Switch Trip Point w c 0 65 0 60 0 60 Low Stage Pressure Switch Trip Point w c 0 30 0 30 0 30 Blower W...

Страница 15: ...0 50 25 55 High S tage P res s ure S witc h Trip P oint w c 0 65 0 60 0 60 Low S tage P res s ure S witc h Trip P oint w c 0 30 0 30 0 30 B lower W heel D x W 10 x 8 10 x 10 10 x 10 B lower Hors epowe...

Страница 16: ...80 Rated External Static w c 10 50 10 50 10 50 Temperature Rise F 30 60 35 65 35 65 High Stage Pressure Switch Trip Point w c 0 55 0 55 0 55 Low Stage Pressure Switch Trip Point w c 0 30 0 30 0 30 Bl...

Страница 17: ...g Speed Tap Adjust Tap Low Stage CFM High Stage CFM Rise F Minus 790 1125 46 Minus 945 1350 49 Normal 875 1250 41 Normal 1050 1500 44 Plus 960 1375 38 Plus 1155 1650 40 Minus 850 1215 43 Minus 1010 14...

Страница 18: ...Minus 540 Minus 720 Minus 720 Normal 600 Normal 800 Normal 800 Plus 660 Plus 880 Plus 880 Minus 720 Minus 990 Minus 990 Normal 800 Normal 1100 Normal 1100 Plus 880 Plus 1210 Plus 1210 Minus 990 Minus...

Страница 19: ...w c and 0 8 w c is tabulated for cooling purposes only 6 Motor CFM maximum ADVC8 Continuous Fan Speed Chart AMVC8 GMVC8 Continuous Fan Speed Chart Model Furnace Maximum CFM Continuous Fan Speed 1 2 A...

Страница 20: ...e CFM Rise F Heating Speed Tap Adjust Tap Low Stage CFM High Stage CFM Rise F Minus 660 945 55 Minus 850 1215 55 Normal 735 1050 49 Normal 945 1350 49 Plus 810 1155 45 Plus 1040 1485 45 Minus 725 1035...

Страница 21: ...ng Speed Tap Adjust Tap CFM 1 Minus 540 Minus 720 Minus 765 Normal 600 Normal 800 Normal 850 Plus 660 Plus 880 Plus 935 Minus 720 Minus 990 Minus 1035 Normal 800 Normal 1100 Normal 1150 Plus 880 Plus...

Страница 22: ...ximum CFM capaibility is 1760 CFM the continuous fan speed will be 0 30 X 1760 CFM 530 CFM Example If the furnace maximum CFM capaibility is 1760 CFM the continuous fan speed will be 0 30 X 1760 CFM 5...

Страница 23: ...FF ramping profiles These profiles may be used to enhance cooling performance and increase comfort level The ramping profiles are selected using DIP switches 5 and 6 Refer to the following figure for...

Страница 24: ...shown on rating plate 5 Do not operate above 0 5 w c ESP in heating mode Operating between 0 5 w c and 0 8 w c is tabulated for cooling purposes only 6 Motor CFM maximum 100 CFM OFF OFF Profile C ramp...

Страница 25: ...30 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPU...

Страница 26: ...IFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING ONLY C AIR CLEANER HIGH FIRE PRESS SWTICH INDOOR HUMIDIFIER PK PINK WH 9 IND LO 14 Y2 40 VA 3 HUM YL JUNCTION BLWR PU PURPLE 1 CIRCULATOR BLOW ER R...

Страница 27: ...NTROLS HUM YL JUNCTION BLWR PU PURPLE 1 CIRCULATOR BLOWER R 1 GND JUNCTION BOX SWITCH TEMP NEUTRAL 115kBTU MODELS BLOWER COMPARTMENT DOOR SWITCH OPEN WHEN DOOR OPEN C LINE BK YL NEUTRAL 4 NEUTRAL POLA...

Страница 28: ...0 AUTOMATIC IGNITION SYSTEM 24VAC 60Hz 0 8 A MAX 15 12 GND 13 9 G TX 2 O G 1 59 4715 REV F Y2 7 W1 3 W2 C IND LO 2 RX IND HI Y 1 Y1 O 1 G O DEHUM R R IND N HUM ST5 ST4 HUM C FS Y 2 1 DE HUM Y2 10 W 1...

Страница 29: ...ference only Not all wiring is as shown above Refer to the appropriate wiring diagram for the unit being serviced Wiring is subject to change Always refer to the wiring diagram on the unit for the mos...

Отзывы: