FURNACE SPECIFICATIONS
1.
These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.
2.
For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.
3.
The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.
4.
Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps.
16
ADVC8
MODEL
ADVC80703BX**
ADVC80905CX**
ADVC81155CX**
Btuh Input (US) High Fire
70,000
90,000
115,000
Output (US) High Fire
56,000
72,000
92,000
Btuh Input (US) Low Fire
51,000
63,000
80,500
Output (US) Low Fire
40,800
50,400
64,400
A.F.U.E.
80%
80%
80%
Rated External Static (" w.c.)
.10 - .50
.10 - .50
.10 - .50
Temperature Rise (°F)
30 - 60
35 - 65
35 - 65
High Stage Pressure Switch Trip Point (" w.c.)
-0.55
-0.55
-0.55
Low Stage Pressure Switch Trip Point (" w.c.)
-0.30
-0.30
-0.30
Blower W heel (D" x W ")
10 x 8
10 x 10
10 x 10
Blower Horsepower
3/4
3/4
3/4
Blower Speeds
Max CFM @ 0.5 E.S.P.
Power Supply
115-60-1
115-60-1
115-60-1
Minimum Circuit Ampacity (MCA)
12.1
12.1
12.1
Maximum Overcurrent Device
15
15
15
Transformer (VA)
40
40
40
Heat Anticipator (Amps)
0.7
0.7
0.7
Primary Limit Setting (°F)
190
190
200
Auxiliary Limit Setting (°F)
120
120
120
Rollout Limit Setting (°F)
300
300
300
Fan Delay On Heating
30 secs.
30 secs.
30 secs.
Off Heating *
150 secs.
150 secs.
150 secs.
Fan Delay On Cooling
5 secs.
5 secs.
5 secs.
Off Cooling
45 secs.
45 secs.
45 secs.
Fan Delay On - Fan Only
5 secs.
5 secs.
5 secs.
Gas Supply Pressure (Natural/Propane) (" w.c.)
7 / 11
7 / 11
7 / 11
Manifold Pressure (Natural/Propane) High Stage (" w.c.)
3.5 / 10
3.5 /10
3.5 /10
Manifold Pressure (Natural/Propane) Low Stage ("w.c.)
1.9 / 6.0
1.9 / 6.0
1.9 / 6.0
Orifice Size (Natural/Propane)
#43 / #55
#43 / #55
#43 / #55
Number of Burners
3
4
5
Vent Connector Diameter (inches)
4
4
4
Shipping W eight (lbs.)
112
124
130
Refer to airflow charts in this manual.
* Off Heating - This fan delay tim ing is adjus table (90, 120, 150 or 180 s econds ), 150 s econds as s hipped.