ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
12.6
26
COMFORT CONTROL
2
SYSTEM™
CONTROL WIRING
AND
CONVENTIONAL THERMOSTAT WIRING
ICC DIAGNOSTIC CODES
Dual 7-Segment
LEDs Display
Code
Diagnostic Description
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
• The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
• Wait until unit timer has expired or press the
TEST button to defeat short cycle delay.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
• The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
• Wait unit timer has expired or press the TEST
button to defeat short cycle delay.
h - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
Status/Possible Cause – Troubleshooting
Information
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic
Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
•
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode
The ICC is in TEST mode
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic
Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
•
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode
The ICC is in TEST mode
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic
Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
•
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode
The ICC is in TEST mode
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic
Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
•
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode
The ICC is in TEST mode
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic
Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
•
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode
The ICC is in TEST mode
h – Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
• The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
• Wait unit timer has expired or press the TEST
button to defeat short cycle delay.
H – Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
H – Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
• The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
• Wait unit timer has expired or press the TEST
button to defeat short cycle delay.
3
Lower case “c” indicates first stage cooling operation
2)
Second Stage Cooling Operation
– When the ICC receives a command for second stage
cooling operation, an upper case “C” is displayed on the 7-segment LEDs.
Upper case “C” indicates second stage cooling operation
3)
First Stage Heating Operation
- When the ICC receives a command for first stage
heating operation, “h1” is displayed on the 7-segment LEDs.
“h1” indicates first stage heating operation
4)
Second Stage Heating Operation
- When the ICC receives a command for second stage
heating operation, “h2” is displayed on the 7-segment LEDs.
“h2” indicates second stage heating operation
5)
Defrost Operation
– When the ICC starts a defrost cycle, a lower case “d” is displayed
on the 7-segment LEDs.
Lower case “d” indicates defrost operation (in heating mode)
3-minute Anti-short Cycle Timer
d – Defrost Active
The unit is undergoing a defrost cycle
Normal operation
11
d1 – No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch
The indoor air mover (air handler/furnace)
cannot supply the required airflow for
proper system operation
•
Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P – Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
•
Motor protector open
•
Line voltage disconnected
01 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
•
Low refrigerant charge
•
Air ducts have substantial leakage
•
Dirty indoor air filter
•
Dirty outdoor coil
02 – High Pressure Control Open
The ICC detects the HPC is open.
Reference ICC codes:
•
21
•
L21
•
29
•
L29
03 – Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
•
Check thermostat wire connections (R, C, 1, &
2)
•
Check thermostat location in zone (too close to
discharge grill)
L4 – Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the
average run time for each trip is less than 15
seconds
•
Bad run capacitor
•
Low line voltage
•
Excessive refrigerant in compressor
•
Seized bearings in compressor
05 – Open Circuit (Compressor will not
Run)
•
The ICC has received a command for
unit operation but no current is present in
the start and run circuits.
•
The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
•
Check for damaged, miswired, or wrong run
capacitor
•
Check for broken wires, loose connectors, or
miswired compressor
•
Check compressor windings for continuity
•
Check for open compressor internal protector
06 – Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
•
Check for damaged, miswired, or wrong run
capacitor
•
Check for broken wires, loose connectors, or
miswired compressor
•
Check compressor windings for continuity
07 – Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
•
Check for damaged, miswired, or wrong run
capacitor
•
Check for broken wires, loose connectors, or
miswired compressor
•
Check compressor windings for continuity
09 – Low Secondary Volts
The secondary voltage at R and C is below
18VAC
•
Control transformer overloaded
•
Low line voltage
3
Lower case “c” indicates first stage cooling operation
2)
Second Stage Cooling Operation
– When the ICC receives a command for second stage
cooling operation, an upper case “C” is displayed on the 7-segment LEDs.
Upper case “C” indicates second stage cooling operation
3)
First Stage Heating Operation
- When the ICC receives a command for first stage
heating operation, “h1” is displayed on the 7-segment LEDs.
“h1” indicates first stage heating operation
4)
Second Stage Heating Operation
- When the ICC receives a command for second stage
heating operation, “h2” is displayed on the 7-segment LEDs.
“h2” indicates second stage heating operation
5)
Defrost Operation
– When the ICC starts a defrost cycle, a lower case “d” is displayed
on the 7-segment LEDs.
Lower case “d” indicates defrost operation (in heating mode)
3-minute Anti-short Cycle Timer
FLASHING
FLASHING
H
H
t - Test Mode
The ICC is in TEST mode
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic
Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
•
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
•
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
•
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode
The ICC is in TEST mode