LOSS OF LUBRICATION
SYMPTOMS
POSSIBLE CAUSE
CHECK OR REMEDIES
Compressor failures
Line tubing too long
Add oil to the recommended level
Line tubing too large
Reduce pipe size to improve
oil return
Low suction pressure
Low charge
Check system charge
Refrigerant leaks
Repair and recharge
Cold, Noisy compressor - Slugging
Dilution of Oil with Refrigerant
Observe piping guidelines
Noisy compressor
Migration
Check crankcase heater
Cold, sweating compressor
Flooding
Check system charge
Low Load
Reduced air flow
Dirty filter
Dirty coil
Wrong duct size
Restricted duct
Thermostat setting
Advise customer
Short cycling of compressor
Faulty pressure control
Replace control
Loose wiring
Check all control wires
Thermostat
In supply air stream,
out of calibration,
Customer misuse
FLOODED STARTS
SYMPTOMS
POSSIBLE CAUSES
CHECK OR REMEDIES
Liquid in the compressor shell
Faulty or missing crankcase heater
Replace crankcase heater
Too much liquid in system
Incorrect piping
Check Piping guidelines
Overcharge
Check and adjust charge
SLUGGING
SYMPTOMS
POSSIBLE CAUSES
CHECK OR REMEDIES
On start up
Incorrect piping
Review pipe size guidelines
TEV hunting when running
Oversized TEV
Check TEV application
FLOODING
SYMPTOMS
POSSIBLE CAUSES
CHECK OR REMEDIES
Poor system control
Loose sensing bulb
Secure the bulb and insulate
using a TEV
Bulb in wrong location
Relocate bulb
Wrong size TEV
Use correct replacement
Improper superheat setting
Adjust, if possible;
Replace, if not
Poor system control
Overcharge
Check system charge
using capillary tubes
High head pressures
Dirty heat pump
Restricted air flow
Recirculation of air
Evaporator air flow too low
Adjust air flow to 400 CFM/Ton
48