– copper to copper - 5%
– Silver alloy (no flux)
– copper to steel or brass - 35%
– silver alloy (with flux)
•
Be certain both refrigerant shutoff valves at the outdoor unit are closed.
•
Clean the inside of the fittings and outside of the tubing with steel wool or sand
cloth before soldering. Always keep chips, steel wool, dirt, etc., out of the inside
when cleaning.
•
Assemble tubing part way into fitting. Apply flux all around the outside of the
tubing and push tubing into stop. This procedure will keep the flux from getting
inside the system.
•
Remove the cap and schrader core from service port to protect seals from heat
damage.
•
Use an appropriate heatsink material around the copper stub and the service
valves before applying heat.
•
IMPORTANT:
Do not braze any fitting with the TEV sensing bulb attached.
•
Braze the tubing between the outdoor unit and indoor coil. Flow dry nitrogen
into a service port and through the tubing while brazing.
•
After brazing – use an appropriate heatsink material to cool the joint and
remove any flux residue.
•
The service valves are not backseating valves. To open the valves, remove the
valve cap with an adjustable wrench. Insert a 3/16” or 5/16” hex wrench into the
stem. Back out counterclockwise.
•
Replace the valve cap finger tight then tighten an additional 1/2 hex flat for a
metal-to-metal seal.
7.6 Leak Testing
•
Pressurize line set and coil through service fittings with dry nitrogen to 150
PSIG maximum. Leak test all joints using liquid detergent. If a leak is found,
recover pressure and repair.
8.0 DEMAND DEFROST CONTROL
The ICC has a demand defrost algorithm so a separate defrost control is not need-
ed. The ICC monitors the outdoor ambient temperature, outdoor coil temperature,
and the compressor run-time to determine when a defrost cycle is required.
8.1 Defrost Initiation
A defrost will be initiated when the three conditions below are satisfied:
1) The outdoor coil temperature is below 35°F.
2) The compressor has operated for at least 34 minutes with the outdoor coil tem-
perature below 35°F.
3) The defrost algorithm determines a defrost is required.
Additionally, a defrost will be initiated if six hours of accumulated compressor run-
time has elapsed without a defrost with the outdoor coil temperature below 35°F.
!
WARNING
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE SYSTEM FOR
LEAK TEST. OXYGEN REACTS VIOLENTLY WITH OIL, WHICH CAN
CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR
DEATH.
15
Содержание PRL-series
Страница 52: ...FIGURE 11 WIRING DIAGRAM FOR 2 3 4 TON 19 0 WIRING DIAGRAMS 52 ...
Страница 53: ...FIGURE 12 WIRING DIAGRAM FOR 5 TON 53 ...
Страница 54: ...54 ...
Страница 55: ...55 ...
Страница 56: ...56 CM 1108 ...