Controlling the unit
30
7. Controlling the unit
The unit is controlled by using the controls of the device that is to be cooled.
All alarm and error signaling is only indicated on the control panel of the device that is to be cooled.
To show the status of the unit multiple LEDs are available directly at the unit. Alert and error mes-
sages are shown at the display of the unit and, if available, at the device that is to be cooled.
7.1. Switching on the unit
Switching on the unit
Requirements
The unit is ready to be switched on.
Procedure
Switch on the unit about 1 minute prior to operation of the device to be cooled.
Check whether the operating specifications are met, see "Technical specifications".
The unit has been switched on.
7.2. Switching off the unit
Switching off the unit
Requirements
Cooling operation finished.
Procedure
Switch of the unit using the power button.
Close all valves that may exist in the extension of the hoses running to and from the
unit.
The unit has been switched off.
7.3. Settings
NOTE
The monitoring units are set according to technical specifications and sealed. Any modifications to
these settings lie in the sole responsibility of the customer and must only be carried out by expert
staff.
7.3.1. Flow switch
NOTE
The adjusting of the flow switch should not be made without the help of proper measuring equipment,
as the switching point must be adjusted in a controlled way. Otherwise the function of the safety cir-
cuit might not be reliable and, as a result, the device to be cooled might get damaged.
The flow switch is equipped with a closing contact. The flow switch opens when the flow falls below
an adjusted quantity. The set switch-off threshold: see "Technical specifications"