14
IE-SNC-T3110-09
General
Power supply voltage:
9 to 30 Vdc
Current output in case of error:
< 3.8 mA or > 22 mA
Recommended calibration interval:
1 year (
relative humidity 1 year, temperature 2 years
)
Protection:
housing with electronics IP65, sensors are located in cover with
IP40 protection
Storage temperature range:
-3
0 to +80 °C
Storage relative humidity range:
5 to 95 %RH (no condensation)
Certification of T3110Ex transmitter:
Certificate:
FTZÚ 13 ATEX 0189X
Marking: ll 3G Ex ic llC T6 Gc
Compliance with standards: EN 60079-0:2018 and EN 60079-11:2012
Intrinsically safe parameters of current loops I1 and I2:
Ui = 30 V, Ii = 100 mA, Io = 22 mA, Ci ~ 0, Li ~0
Special condition for safe use
(sign “X”): Under certain extreme
circumstances, the plastic enclosure may store an
ignition-capable level of electrostatic charge. The
device shall not be installed in a location where the
external conditions are conducive to the build-up of
electrostatic charge. The equipment shall only be
cleaned with a damp cloth.
Electromagnetic compatibility:
EN 61326-1
Weight:
approximately 150 g
Housing material:
ABS