background image

 If LCD is switched OFF

, after remaining battery capacity is displayed 

LCD switches OFF. Only symbol LOG is displayed if logger is switched 
ON. Symbol LOG blinks, if data memory is filled for more than 90%. 
If logger is operated with LCD switched OFF in the mode, when record 
works only if alarm is active, symbol LOG is replaced by the neighbor 
symbol 

– 

(hyphen). It appears in case, counter value is at set limits and 

logging is stopped. Displayed symbol indicates logger is switched ON. 
 

 
If logger LCD is switched OFF, short display is enabled by the magnet (this is not possible if  

logger is operated with permanently connected communication adapter). Insert magnet to slots at 
the side of the logger and wait for about 4 seconds. If logger has enabled the function of switching 
OFF by magnet, do not remove magnet from slots before indication decimal point goes out – logger 
would be switched OFF! Display goes out automatically after 30 s. Remove magnet from slots 
anytime during display is ON or later. 

 
Activation of switched OFF LCD for 30 seconds by the magnet 
 

 

 

 

Alarm indication on the LCD 

Allow alarm evaluation from the PC program and set lower and upper alarm limit of the 

counter input (binary input has no alarm function). If counter values are at range inside of the set 
limits, alarm is not active. If counter value exceeds any of set limits, alarm will be activated and 
indicated on the LCD. Alarm function has two modes: instant or with memory (detected alarm is 
indicated permanently till alarm memory is cleared from the PC (useful if counter overflow is 
enabled). 

 
Active alarm is indicated (if LCD is ON) by blinking of the counter value 
on the LCD and by arrow 3 at the LCD upper side. 

Notice:

 if logger is operated at low temperature (below approximately 

-5 °C), alarm indication by blinking can be indistinct. Indication by arrows 
works correctly. 
 

IE-LOG-S7021-04 

 

  7 

Содержание S7021

Страница 1: ...LOGGER S7021 Dual channel logger with counter and binary inputs Instruction for use...

Страница 2: ...aximum value and logger is switched OFF with the message on the LCD If needed counter mode can be selected when after fulfilling counter overflows and continues from value 0 Logging mode can be adjust...

Страница 3: ...me clock adjustable from computer integrated calendar including leap years Error of internal RTC 200 ppm i e 0 02 17 28 s in 24 h Power Lithium battery 3 6 V size AA Battery life typical data download...

Страница 4: ...setting of the instrument accordingly to the user needs menu Configuration Setting of instrument parameters Before logging start it is necessary check or optionally set the logger real time clock sele...

Страница 5: ...e logger LCD indication ON and OFF is displayed permanently Selection of display of increments at the card of counter channel setting causes record of counter increments in time specified by logging i...

Страница 6: ...mperature range battery life can be reduced to 75 i e if displayed remaining battery capacity drops below 25 it is recommended to replace the battery If LCD is switched ON actual readings are displaye...

Страница 7: ...ation decimal point goes out logger would be switched OFF Display goes out automatically after 30 s Remove magnet from slots anytime during display is ON or later Activation of switched OFF LCD for 30...

Страница 8: ...clock setting below critical limit or battery disconnection for longer period than approximately 30 s after display switch ON during date and time display all four arrows appears as warning to check o...

Страница 9: ...s identical with the above procedure for switching ON If decimal point does not appear after 1 s it is necessary remove the magnet and repeat the procedure Logger connection to monitored device by the...

Страница 10: ...l logger settings remain unchanged In the opposite case check by means of PC program all settings especially the real time clock in logger Attention inserted battery with incorrect polarity causes log...

Отзывы: