IM-NT-2.3
Operator Guide ©ComAp
– January 2018
6
IM-NT-2.3 Operator Guide.pdf
Conformity
Declaration
Following described machine complies with the appropriate basic safety and health
requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type,
as brought into circulation by us.
WARNING
– VERY IMPORTANT!!!
For BTB
Every time you want to disconnect the following InteliMains controller
terminals:
•
Bus voltage measuring and / or
•
Binary outputs for BTB control and / or
•
BTB feedback
switch InteliMains to MAN mode!
For MCB/MGCB
Every time you want to disconnect the following InteliMains controller
terminals:
•
Mains voltage measuring and / or
•
Binary outputs for MCB control and / or
•
MCB feedback
switch InteliMains to MAN mode!
!!! CAUTION !!!
Dangerous Voltage
In no case touch the terminals for voltage and current measurement!
Always properly connect grounding terminals!
Take care when disconnecting In/Im3 terminals when the gen-set is stopped.
For safety connect parallel to controller In/Im3 terminals two anti parallel diodes 10A/100V.
In any case do not disconnect generator CT terminals when the gen-set is loaded.
Adjust Set Points
All setpoints are preadjusted to th
eir typical values. But the setpoints in the “
Basic settings
”
settings group
!!must!!
be adjusted before the first startup of the gen-set.
!!! WRONG ADJUSTMENT OF BASIC PARAMETERS
CAN DESTROY THE GEN-SET !!!
The following instructions are for qualified personnel only.
To avoid personal injury do not perform any action not specified in this manual !!!
Adjust set points
All parameters are preadjusted to their typical values. But the set points in the “
Basic settings
”
settings group
!!must!!
be adjusted before the first startup of the gen-set.
!!! WRONG ADJUSTMENT OF BASIC PARAMETERS
CAN DESTROY THE GEN-SET !!!
The following instructions are for qualified personnel only.