5005749-CTG-A-0216
4
Johnson Controls Unitary Products
CHARGING PROCEDURES:
1. Check the Factory Unit Charge listed on the unit nameplate to verify the refrigerant charge for the outdoor unit, the smallest matched indoor unit, and the 15 feet of
interconnecting lineset.
2. Verify the indoor metering device and additional charge required for the specific matched indoor unit in the system using the above table.
3. Add additional charge for the amount of interconnecting lineset greater than 15 feet at the rate specified in the Physical and Electrical Table.
4. For installations requiring additional charge, weigh in refrigerant for the specific matching indoor unit and actual lineset length.
5. Once the charge adders for matched indoor unit and for lineset have been weighed in, verify the system operation against the temperatures and pressures in the
Charging Chart for the outdoor unit. Locate Charging Charts on the outdoor unit and also in the Service Data Application Guide on
www.upgnet.com
. Follow the
Subcool or the Superheat charging procedure in the Installation Manual according to the type of indoor metering device in the system, and allow ten minutes after
each charge adjustment for the system operation to stabilize. Record the charge adjustment made to match the Charging Chart.
6. Permanently stamp the unit data plate with the TOTAL SYSTEM CHARGE defined as follows: TOTAL SYSTEM CHARGE = Base Charge (as shipped) + charge
adder for matched indoor unit + charge adder for actual lineset charge adjustments to match the Charging Chart.
SYSTEM CHARGE FOR VARIOUS MATCHED SYSTEMS
Outdoor Unit
TH4B1821S TH4B2421S TH4B3021S TH4B3521S TH4B3621H TH4B4221H TH4B4821S TH4B6021S
Required TXV
1
,
2
1. For applications requiring a TXV, use S1-1TVM*** series kit.
2. A TXV kit must be used with these indoor units to obtain system performance.
BA1
BA1
BB1 or BE1
BE1
BF1
BF1
BC1
BG1
Defrost Jumper Pin Setting
2
2
2
3
3
2
4
2
Indoor Unit
3,4,5
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit S1-2FD06700224.
4. CF coils cannot be used in horizontal applications.
5. Charge adders shown above do not indicate that coils are rated for every application. Refer to Performance Data Tables for actual performance for specified
system matches. Obtain certified system ratings from
www.ahridirectory.org
.
Additional Charge, oz
AP18B
0
–
–
–
–
–
–
–
AP24B
7
0
–
–
–
–
–
–
AP30B
–
–
0
–
–
–
–
–
AP36B
–
–
0
–
–
–
–
–
AP36C
–
–
3
–
–
–
–
–
AP37C
–
–
–
–
8
–
–
–
AP42C
–
–
–
–
–
–
–
–
AP48(C,D)
–
–
–
–
–
–
–
–
AP60(C,D)
–
–
–
–
–
–
–
–
AE18B
0
–
–
–
–
–
–
–
AE24B
7
0
–
–
–
–
–
–
AE30B
–
9
–
–
–
–
–
–
AE36(B,C)
–
–
0
–
–
–
–
–
AE42C
–
–
–
7
8
0
–
–
AE48(C,D)
–
–
–
–
8
0
0
–
AE60C
–
–
–
–
–
1
8
–
AE60D
–
–
–
–
–
–
–
2
AVC18B
0
–
–
–
–
–
–
–
AVC24B
7
0
–
–
–
–
–
–
AVC30B
–
9
0
–
–
–
–
–
AVC36(B,C)
–
–
0
0
–
–
–
–
AVC42C
–
–
–
7
8
0
–
–
AVC48(C,D)
–
–
–
–
8
0
0
–
AVC60C
–
–
–
–
–
1
8
–
AVC60D
–
–
–
–
–
–
–
2
CF/CM/CU18(A,B)
0
–
–
–
–
–
–
–
CF/CM/CU24(A,B)
7
0
–
–
–
–
–
–
CF/CM/CU30(A,B,C)
–
9
–
–
–
–
–
–
CF/CM/CU36(A,B,C)
–
–
0
0
–
–
–
–
CF/CM/CU42(B,C,D)
–
–
3
8
–
–
–
–
CF/CM/CU48(C,D)
–
–
–
7
8
0
0
–
CF/CM/CU60(C,D)
–
–
–
–
–
1
8
–
CF/CM64D
–
–
–
–
–
–
–
2
Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil
only matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.
FOOTNOTES: