5005749-CTG-A-0216
Johnson Controls Unitary Products
43
PERFORMANCE DATA - 2.5 TON
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
65 °F
75 °F
85 °F
95 °F
105 °F
115 °F
125 °F
T (°F)
P (PSIG)
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
TH4B3021S
35
107
26.6
1.45
24.8
1.62
23.0
1.79
21.2
1.95
19.4
2.12
17.6
2.29
15.8
2.46
40
119
30.0
1.43
28.0
1.61
26.0
1.80
23.9
1.98
21.9
2.16
19.9
2.35
17.9
2.53
45
130
33.4
1.41
31.1
1.61
28.9
1.81
26.7
2.01
24.5
2.20
22.2
2.40
20.0
2.60
50
143
36.7
1.39
34.3
1.60
31.9
1.82
29.4
2.03
27.0
2.25
24.5
2.46
22.1
2.67
55
156
40.1
1.37
37.5
1.60
34.8
1.83
32.2
2.06
29.5
2.29
26.9
2.52
24.2
2.74
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TH4B3021S
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
IDCFM
800
1000
1200
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
27.2
29.1
29.5
31.1
32.4
28.4
29.5
29.7
31.3
32.2
29.7
29.9
29.9
31.4
32.1
S.C.
27.0
24.3
21.0
19.8
15.4
28.2
26.0
22.4
21.0
15.9
29.5
27.8
23.7
22.2
16.5
KW
1.75
1.76
1.77
1.77
1.77
1.83
1.84
1.84
1.84
1.85
1.90
1.91
1.91
1.92
1.92
75
T.C.
26.9
28.3
28.8
31.6
34.0
28.5
29.2
29.4
32.1
34.0
30.0
30.0
29.9
32.6
34.0
S.C.
26.6
24.3
20.9
20.7
16.3
28.2
26.9
23.0
22.7
17.3
29.8
29.5
25.0
24.6
18.2
KW
1.91
1.93
1.93
1.93
1.92
1.98
2.00
2.00
2.00
2.00
2.06
2.07
2.07
2.08
2.08
85
T.C.
25.7
27.0
27.2
30.1
32.9
27.2
27.8
27.8
30.6
33.1
28.7
28.6
28.4
31.0
33.4
S.C.
25.5
23.5
20.0
20.1
15.9
27.0
25.9
22.1
22.1
17.1
28.6
28.4
24.2
24.1
18.2
KW
2.12
2.14
2.13
2.13
2.12
2.19
2.21
2.21
2.21
2.20
2.26
2.27
2.28
2.28
2.27
95
T.C.
24.5
25.7
25.6
28.6
31.7
26.0
26.5
26.3
29.0
32.3
27.4
27.2
26.9
29.4
32.8
S.C.
24.3
22.7
19.1
19.5
15.5
25.8
25.0
21.2
21.5
16.9
27.3
27.2
23.3
23.5
18.2
KW
2.34
2.35
2.34
2.34
2.33
2.40
2.42
2.41
2.41
2.40
2.47
2.48
2.49
2.48
2.47
105
T.C.
23.2
24.1
24.0
26.8
29.7
24.5
24.9
24.5
27.2
30.1
25.8
25.7
25.1
27.5
30.6
S.C.
23.0
21.9
18.2
18.8
14.8
24.4
23.8
20.3
20.8
16.1
25.7
25.7
22.3
22.8
17.4
KW
2.65
2.66
2.65
2.65
2.63
2.71
2.72
2.72
2.72
2.70
2.77
2.78
2.79
2.79
2.77
115
T.C.
21.9
22.6
22.4
25.1
27.7
23.1
23.4
22.9
25.4
28.1
24.3
24.2
23.3
25.7
28.4
S.C.
21.7
21.0
17.4
18.0
14.1
23.0
22.6
19.4
20.1
15.4
24.2
24.2
21.4
22.2
16.7
KW
2.95
2.95
2.95
2.95
2.93
3.01
3.02
3.02
3.01
2.99
3.07
3.08
3.09
3.08
3.06
125
T.C.
20.6
21.1
20.8
23.4
25.8
21.7
21.9
21.2
23.7
26.1
22.8
22.7
21.6
23.9
26.3
S.C.
20.4
20.2
16.5
17.3
13.4
21.6
21.5
18.5
19.4
14.7
22.7
22.7
20.5
21.5
15.9
KW
3.24
3.25
3.25
3.24
3.22
3.31
3.31
3.32
3.31
3.29
3.37
3.37
3.38
3.38
3.35
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.