5005749-CTG-A-0216
Johnson Controls Unitary Products
61
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
TH4B4221H
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
AIR TEMP.
ENTERING
INDOOR COIL (°F)
ID CFM
1100
1200
1300
MBH
COP
KW
MBH
COP
KW
MBH
COP
KW
60
60
50.8
4.38
3.40
51.6
4.47
3.38
52.3
4.58
3.35
70
48.1
3.98
3.54
49.0
4.07
3.53
49.9
4.15
3.52
80
45.5
3.62
3.68
46.4
3.70
3.68
47.4
3.77
3.68
47
60
41.7
4.01
3.05
42.7
4.10
3.05
43.7
4.20
3.05
70
39.9
3.66
3.19
40.7
3.73
3.19
41.4
3.79
3.20
80
38.0
3.34
3.34
38.6
3.39
3.34
39.2
3.44
3.34
40
60
38.1
3.85
2.90
38.7
3.91
2.90
39.3
3.97
2.90
70
36.2
3.50
3.03
36.8
3.55
3.03
37.3
3.60
3.04
80
34.3
3.18
3.16
34.8
3.22
3.17
35.4
3.26
3.18
30
60
32.4
3.54
2.68
32.4
3.56
2.67
32.4
3.56
2.67
70
30.6
3.23
2.78
30.8
3.25
2.78
31.0
3.26
2.79
80
28.8
2.93
2.88
29.2
2.95
2.90
29.6
2.98
2.91
17
60
24.4
3.05
2.34
24.3
3.02
2.35
24.1
3.00
2.36
70
21.6
2.72
2.33
21.3
2.68
2.33
21.0
2.63
2.34
80
18.9
2.39
2.32
18.4
2.33
2.32
17.9
2.26
2.32
10
60
15.7
2.37
1.94
15.4
2.32
1.95
15.18
2.27
1.96
70
14.7
2.16
2.00
16.0
2.25
2.08
17.3
2.33
2.17
80
13.8
1.97
2.05
16.6
2.20
2.21
19.4
2.38
2.38
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Yellow shaded cells are AHRI High Heating conditions.
Orange shaded cells are AHRI Low Heating conditions.
COIL MULTIPLIERS - 3.5 TON
Air Handler
Coil
MBH
COP
KW
AE42CX21
CF/CM42C
0.98
0.96
1.02
AE48CX21
–
0.99
0.97
1.02
AE48DX21
–
0.99
0.98
1.01
AE60CX21
–
1.01
0.94
1.07
AVC42CX21
–
1.00
0.96
1.04
AVC48CX21
–
0.99
0.96
1.03
AVC48DX21
–
0.99
0.97
1.02
AVC60CX21
–
0.99
0.98
1.02
ME14DN21
CF/CM48D
1.00
0.98
1.02
ME14DN21
CF/CM60D
0.99
0.99
1.00
ME16CN21
CF/CM48C
1.00
0.99
1.02
ME16CN21
CF/CM60C
0.99
0.98
1.01
ME20DN21
CF/CM48D
0.98
0.96
1.02
ME20DN21
CF/CM60D
0.98
0.96
1.02
MVC14DN21
CF/CM48D
0.99
0.96
1.03
MVC14DN21
CF/CM60D
1.00
0.98
1.03
MVC16CN21
CF/CM48C
0.99
0.98
1.02
MVC20DN21
CF/CM48D
0.99
0.97
1.03
MVC20DN21
CF/CM60D
0.99
0.98
1.00