8 | Electrical installation
48 / 88
Operating instructions CMVpro 125-400 ATEX | Version 1-en
WARNING
Risk of injury due to high contact voltage
Injury by electric shock.
▪ If long cable shields are not connected/grounded, high contact voltages can
occur during operation.
u
Connect cable shields of motor connection cables and signal lines to a com-
mon reference potential.
u
Do not use protective earth connections for shielding purposes.
WARNING
Risk of injury due to dangerous residual voltage
Injury by electric shock.
▪ After the fan has been switched off, dangerous residual voltage is still
present in the frequency converter.
u
The operating instructions of the frequency converter provide information
about the time to be observed until this residual voltage has dropped to a
safe value.
u
Before beginning work on the electrical components, always establish an
electrically safe work condition of the frequency converter.
8.3.1
Frequency converter (FC) installation options
For CMVpro 125-400 type centrifugal fans, different executions of electric mo-
tors (IM, PM, EC) can be selected as a drive:
• IM ... Standard asynchronous motor/three-phase motor
• PM ... Permanent magnet motor
• EC ... Brushless DC motor