Digital fire detection control panel
COMPACT LYON PLUS
72
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
3.2.3.3.2.2.- Relay Auto. Configuration...............................................................................Menu_18
Option that allows us to configure all relay automatically (all types like SIRAY, MDA1Y, MDA2Y and
MYOA/F) except SIRDR, like immediate ALARM. This option overrides the previous relay configurations.
3.2.3.3.2.3.- Delete Configured Relays................................................................................Menu_18
Option that
CLEARS ALL CONFIGURED
relays from the loop.
3.2.3.3.3.- Configure alarm zones. ......................................................................................Menu_19
In this menu we have the option of configuring the various alarm zones into which we will divide the
points of the control panel. When an alarm zone is configured, it is not permissible to include a point in
two different alarm zones.
Within this menu we have five submenus:
CONFIGURE ZONE: The control panel will request the loop number, the first and last
consecutive element included in the alarm zone list. We will be able to introduce 8 lists
into each alarm zone.
MODIFY LISTS: This option allows us to modify one of the alarm zone lists.
DELETE ZONE: The zone configuration is deleted.
LABEL: This provides a description of the zone with a maximum of 20 characters for
its identification in the installation.
VIEW CONFIGURATION: To view the list of points that are included in the alarm
zone.