Digital fire detection control panel
COMPACT LYON PLUS
44
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
1.5.6.3- Control panels network menu……………………………………………Menu_25
In the control panels we can find the next specific control panels network menus:
VIEW CONTROL PANELS: Visualize the set control panels.
RESET CONTROL PANEL NETWORK: Reset all the control panels in the network.
NETWORK KEYS CONFIG: Allow to activate/deactivate the keys ( no delay, silence sounder,
evacuate, manual mode, buzzer ) automatically, only when these are activated/deactivated by
another Control Panel connected in the panel network.
SET CONTROL PANEL NUMBER: Every central must have a
unique number
in network.
Number accepted are between (1-35), but max number of repeater is 15, and 15 control panels
VIEW CONTROL PANEL NUMBER
:
View the current central number
NOTE:
Is due to connect a resistance of 120 ohms between the connectors
A and B of the connected strip of the first an last control panel in network
Figure 18.
Control panels network connection. Max 15
1.6- Accessories.
1.6.1- PC based configuration software.
Software is available for the digital control panel (I-Link), that means of which the user can perform all
the control panel programming in a simple and intuitive way. With this system it will be possible to
maintain the configuration for future use.