CCO122 / CCO222 / CCO322 / CCO422

 

 

PORTUGUÉS 

 

 

 

 

 

  

 FABRICANTE DE PRODUCTOS DE INCÊNDIO 

 

Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA. 

Tlf.: +34 935 862 690 - Fax:+34  936 999 261 - [email protected] - www.cofem.com 

 

 

 

 

- 20 -

 

 
 
 

 

 

 

 

Figura 1.

 Ecrã 

Ventilação Manual

 

 

 

Figura 2.

 Ecrã 

Serviço

 

Содержание CCO110

Страница 1: ...Manual Central CO CO Control Panel Centrale CO REF CCO122 CCO222 CCO322 CCO422 CCO110 CCO115 ...

Страница 2: ...36 999 261 cofem cofem com www cofem com 1 CONTENIDO CONTENTS CASTELLANO Pag 2 CENTRALES CCO122 CCO222 CCO322 Y CCO422 Pag 2 CENTRALES CCO110 Y CCO115 Pag 7 ENGLISH Pag 10 CONTROL PANELS CCO122 CCO222 CCO322 CCO422 Pag 10 CONTROL PANELS CCO110 CCO115 Pag 15 PORTUGUÉS Pag 18 CENTRALE CCO 122 CCO 222 CCO 322 CCO442 Pag 18 CENTRALE CCO 122 CCO 222 CCO 322 CCO442 Dupla ventilação e OPCIONAL baterias P...

Страница 3: ... la línea de detección Pulsadores de mando 1 y 2 Permiten el desplazamiento vertical por las diferentes opciones y líneas del menú También permite incrementar o decrementar los parámetros numéricos 3 ESC MENU Permite retroceder una página de pantalla 4 ENTER Permite avanzar hacia la siguiente página de pantalla o confirmar una selección Manejo de la central En condiciones normales de operación la ...

Страница 4: ...min Retardo Postventilación 4 min Fijo Nivel de Alarma 300 ppm Fijo Retardo Alarma 15 min Programable 10 30 min Las flechas y que aparecen en algunas pantallas de menú indican la existencia de pantallas anteriores y posteriores respectivamente a la pantalla actual Instalación La figura muestra el esquema general de conexionado de los diferentes elementos con la central Se pueden conectar un máximo...

Страница 5: ... de zona ENTER fija ENTER ENTER 1 hora A ZONA 1 VENT MAN F start stop A ZONA 1 VENT MAN H start stop ZONA 1 Conectada fija Ventilacion ZONA 1 Manual Parada Ventilacion ZONA 1 Conectada 1 hora Ventilacion ZONA 1 Manual Parada Ventilacion start ENTER stop ENTER start ENTER stop ENTER Figura 1 Pantalla Ventilación Manual M B SERVICIO On Off Zonas B SERV zona 2 zona 1 zona 3 zona 4 ON_OFF ENTER Selecc...

Страница 6: ...ONA 1 nivel retardo Selección de nivel ENTER Selección de retardo ENTER ENTER ENTER ESC ESC Zona 1 Grabandose Nivel de ventilacion OK Zona 1 Grabandose retardo de ventilacion OK C PROG ZONA 1 nivel retardo C PROG ZONA 1 nivel retardo Figura 3 Pantalla Programación de Ventilación D GRABA RETARDO NO esc SI enter M D PROG ALARMAS Retardo 10 min Selección de retardo ENTER ENTER ESC Zona 1 Retardo Alar...

Страница 7: ...el de Ventilación 2 200 ppm Programable 20 300 ppm y Nivel ventilación 1 Retardo Ventilación 2 10 min Programable 1 30 min y Retardo ventilación 1 Retardo Postventilación 4 min Fijo Nivel de Alarma 300 ppm Fijo Retardo Alarma 15 min Programable 10 30 min 12V 12V Alar Vent Alar Vent Zona2 Zona1 Alar Vent Alar Vent Zona2 Zona1 Vent1 Z1 Vent1 Z2 Vent1 Z3 Z1 Vent1 Z4 Z2 6 1 R2 K1 Q4 D2 D1 D3 R3 K2 Q3 ...

Страница 8: ...e ha superado el Nivel de Ventilación E Led ámbar Indica una avería o una irregularidad en la línea de detección F Led verde Indica que el display muestra concentración de CO ppm G Led verde Indica que el display muestra el Nivel de Ventilación H Led verde Indica que el display muestra el Retardo de Ventilación Pulsadores de mando 1 Selección Display Permite seleccionar el dato mostrado por el dis...

Страница 9: ...ble 20 150 ppm en incrementos de 10 ppm Retardo Ventilación 4 min Programable 1 9 min en incrementos de 1 min Retardo Postventilación 4 min Fijo Nivel de Alarma 300 ppm Fijo Retardo Alarma 15 min Fijo Instalación La figura muestra el esquema general de conexionado de los diferentes elementos con la central Se pueden conectar un máximo de 10 detectores por zona en la central CCO110 y 15 en la centr...

Страница 10: ...tilación 1 50 ppm Fijo Retardo Ventilación 1 4 min Programable 1 9 min Retardo Postventilación 1 4 min Fijo Nivel de Ventilación 2 100 ppm Fijo Retardo Ventilación 2 0 min Fijo Retardo Postventilación 0 min Fijo Nivel de Alarma 200 ppm Fijo Retardo Alarma 0 min Fijo Baterías Las baterías se deben conectar a la entrada de baterías del circuito situada en la parte derecha del circuito fuente de alim...

Страница 11: ...cates Fault or trouble on detection zone External Controls 1 2 To move up and down trough different options and lines of menu Also allows to increase or decrease numerical parameters 3 ESC MENU To go back a display 4 ENTER To move forward next display or confirm a selection Operation of Control Panel Under normal condition display of control panel shows main screen visualizing CO concentration on ...

Страница 12: ...ls 50 ppm Programmable 20 150 ppm on a 10 ppm increase rate Ventilation Delay 4 min Programmable 1 9 min Post ventilation delay 4 min Fixed Alarm Level 300 ppm Fixed Alarm Delay 15 min Programmable 10 30 min Cursors and which appears in some displays of menu indicates that there are previous and next displays respectively than the current one Installation Below picture shows the general connection...

Страница 13: ...art stop fixed A ZONE 1 MAN VENT M A VENTILATION Activate Manual zone 1 zone 2 zone 3 zone 4 A ZONE 1 fixed VENT MODE 1 hour Zone selection ZONE 1 Ventilation Connected fixed ZONE 1 Ventilation Manual Stopped ZONE 1 ZONE 1 Manual Stopped Ventilation Ventilation Connected 1 hour Picture 1 Manual Ventilation display ON_OFF ENTER ENTER on ENTER ENTER off on off On Off Zones B OPER zone 1 zone 2 zone ...

Страница 14: ... zone selection ZONE 1 level ZONE 1 Level 050 ppm C SAVE LEVEL NO esc YES enter NO esc YES enter C SAVE DELAY level delay ZONE 1 ZONE 1 Zone 1 Saving Ventilation level OK Zone 1 Saving ventilation delay OK Delay selection Picture 3 Programming of ventilation display ENTER ENTER ESC Delay selection M D PROG ALARMS Delay 10 min D SAVE DELAY NO esc YES enter M D PROG ALARMS Delay 10 min Zone 1 saving...

Страница 15: ...Fixed Alarm Level 300 ppm Fixed Alarm Delay 15 min Programmable 10 30 min Batteries Batteries must be wired to the to the battery output on the board on the right side of the panel this output is labelled Two 12V batteries series connected Alarm OFF CO Ventilation 2 level Ventilation 1 Delay Ventilation 1 ON Ventilation 1 ON Post ventilation 1 Delay Ventilation 1 OFF Alarm ON Alarm Delay Tiempo Al...

Страница 16: ...entilation Level has been exceed E Amber LED Indicates fault or trouble on detection zone F Green LED Indicates that display is showing a CO concentration ppm G Green LED Indicates that display is showing the Ventilation Level H Green LED Indicates that display is showing the Ventilation Delay temporization External Controls 1 Selección Display To select the information shown in the display CO Con...

Страница 17: ...cture shows the general connection outline of different components It is possible to connect up to 10 sensors per zone in CCO110 panel and up to 15 sensors in CCO115 panel Wiring it is recommended to use cable with 1 5 mm2 of minimum section Maximum length of cable per zone must not exceed 400m in a lineal distribution of sensors NOTE Attention to polarity requirements of CO sensors Parameter Valu...

Страница 18: ...ilation 1 Level 50 ppm Fixed Ventilation 1 Delay 4 min Programmable 1 9 min Post ventilation 1 delay 4 min Fixed Ventilation 2 Level 100 ppm Fixed Ventilation 2 Delay 0 min Fixed Post ventilation 2 delay 0 min Fixed Alarm Level 200 ppm Fixed Alarm Delay 0 min Fixed Batteries Batteries must be wired to the to the battery output on the board on the right side of the panel this output is labelled Two...

Страница 19: ...ão D Led âmbar Indica que se superou o Nível de Ventilação E Led âmbar Indica uma avaria ou uma irregularidade na linha de detecção Botões de comando 1 e 2 Permitem o deslocamento vertical pelas diferentes opções e linhas do menu Também permite aumentar ou diminuir os parâmetros numéricos 3 ESC MENU Permite retroceder uma página de ecrã 4 ENTER Permite avançar para a página seguinte de ecrã ou con...

Страница 20: ...uintes Parâmetro Valor Margem Nível de Ventilação 50 ppm Programável 20 150 ppm Atraso Ventilação 4 min Programável 1 9 min Atraso Pós ventilação 4 min Fixo Nivel de Alarme 300 ppm Fixo Atraso Alarme 15 min Programável 10 30 min As flechas e que aparecem em alguns ecrãs de menu indicam a existência de ecrãs anteriores e posteriores respectivamente ao ecrã actual Instalação A figura mostra o esquem...

Страница 21: ...RTUGUÉS FABRICANTE DE PRODUCTOS DE INCÊNDIO Ctra de Molins de Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 20 Figura 1 Ecrã Ventilação Manual Figura 2 Ecrã Serviço ...

Страница 22: ...INCÊNDIO Ctra de Molins de Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 21 Figura 3 Ecrã Programação de Ventilação Figura 4 Ecrã Programação Atraso de Alarmes Figura 5 Ecrã Recuperar Dados de Origem ...

Страница 23: ... Fixo Nivel de Alarme 200 ppm Fixo Atraso Alarme 0 min Programável 0 30 min Baterias As baterias devem ligar se à entrada de baterias do circuito situado na parte direita do cofre esta saída está identificada Ligação das duas baterias de 12 V em série Alar Vent Alar Vent Zona2 Zona1 Alar Vent Alar Vent Zona2 Zona1 Vent1 Z1 Vent1 Z2 Vent1 Z3 Z1 Vent1 Z4 Z2 6 1 R2 K1 Q4 D2 D1 D3 R3 K2 Q3 Q1 R1 K3 R5...

Страница 24: ...e se superou o Nível de Ventilação E Led âmbar Indica uma avaria ou uma irregularidade na linha de detecção F Led verde Indica que o display mostra concentração de CO ppm G Led verde Indica que o display mostra o Nível de Ventilação H Led verde Indica que o display mostra o Atraso de Ventilação Botões de comando 1 Selecção Display Permite seleccionar o dado mostrado pelo diplay Concentração de Co ...

Страница 25: ... seguintes Parâmetro Valor Margem Nível de Ventilação 50 ppm Programável 20 150 ppm Atraso Ventilação 4 min Programável 1 9 min Atraso Pós ventilação 4 min Fixo Nivel de Alarme 300 ppm Fixo Atraso Alarme 15 min Fixo Instalação A figura mostra o esquema geral de ligação dos diferentes elementos com a central Pode ligar se um máximo de 10 detectores por zona Recomenda se o uso de cabo com uma secção...

Страница 26: ...em Nível de Ventilação 1 50 ppm Fixo Atraso Ventilação 1 4 min Programável 1 9 min Atraso Pós ventilação 1 4 min Fixo Nível de Ventilação 2 100 ppm Fixo Atraso Ventilação 2 0 min Fixo Atraso Pós ventilação 2 0 min Fixo Nivel de Alarme 200 ppm Fixo Atraso Alarme 0 min Fixo Baterias As baterias devem ligar se à entrada de baterias do circuito situada na parte direita do circuito fonte de alimentação...

Страница 27: ...NTE DE PRODUCTOS CONTRA INCENDIOS FIRE PROTECTION MANUFACTURER FABRICANTE DE PRODUCTOS DE INCÊNDIO Ctra de Molins de Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 26 NOTAS NOTES NOTAS ...

Страница 28: ... com sat1 cofem com ventas1 cofem com ventas2 cofem com cofem cofem com Atención Técnico Comercial Ventas 34 902 448 811 34 935 862 690 C S Sales 34 935 862 694 34 902 338 811 sat2 cofem com tecnic cofem com compras cofem com export cofem com Export Fax pedidos S A T Compras 34 935 862 692 34 935 862 693 Technical Commercial Service T A S Purchase Export 34 902 338 811 34 936 999 261 Fax pedidos F...