CCO122 / CCO222 / CCO322 / CCO422
ENGLISH
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
- 14 -
12V
12V
-
+
-
+
-
Double ventilation and (OPTIONAL) batteries
Double ventilation:
If the control panel has double ventilation, then it should be connected according to the
following schematic.
Factory settings are as follows:
Parameter Value
Margins
Ventilation 1 Level:
50 ppm
Programmable
(20
150 ppm)
Ventilation 1 Delay:
4 min
Programmable
(1
9 min)
Post-ventilation 1 delay:
4 min
Fixed
Ventilation 2 Level:
200 ppm
Programable
(20
300 ppm) and
Ventilation 1 level
Ventilation 2 Delay:
10 min
Programable
(1
30 min) and
Ventilation 1 delay
Post-ventilation 2 delay:
4 min
Fixed
Alarm Level:
300 ppm
Fixed
Alarm Delay:
15 min
Programmable
(10
30 min)
Batteries:
Batteries must be wired to the to the battery output
on the board on the right side of the panel, this
output is labelled.
Two 12V-batteries series-connected:
Alarm
OFF
[CO]
Ventilation 2
level
Ventilation 1
Delay
Ventilation 1
ON
Ventilation 1
ON
Post-ventilation 1
Delay
Ventilation 1
OFF
Alarm
ON
Alarm
Delay
Tiempo
Alarm
level
Ventilation 2
Delay
Ventilation 2
ON
Ventilation 2
ON
Post-ventilation 2
Delay
Ventilation 2
OFF
Ventilation 1
level
Alar
Vent
Alar
Vent
Zona2
Zona1
+
-
+
-
+
+
-
-
Alar
Vent
Alar
Vent
Zona2
Zona1
+
-
+
-
+
+
-
-
V
e
n
t1
Z
1
V
e
n
t1
Z
2
V
e
n
t1
Z
3(
*Z
1)
V
e
n
t1
Z
4(
*Z
2)
6
1
R2
K1
Q4
D2
D1
D3
R3
K2
Q3
Q1
R1
K3
R5
K5
R4
1
U5
K4
J4
1
U1
Q5
U3
1
U4
1
U2
D4
D5
Q2
-
+
AL
Z4
Z3
Z2
Z1
Vent2Z4
-
+
J1
GN
D
C
PU
V
e
n
t2
Z
2
V
e
n
t2
Z
3
V
e
n
t2
Z
1
V
e
n
t2
Z
4
Baterías
+
-
BAT
Vent2Z2 Vent2Z3
Vent2Z1
A
la
rm
a
Z
4(
*Z
2)
A
la
rm
a
Z
3(
*Z
1)
A
la
rm
a
Z
2
A
la
rm
a
Z
1
In case of 1 or 2 zones Control Panel, you have to follow indications with *