CCO110 / CCO115
ENGLISH
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
- 17 -
Double ventilation and (OPTIONAL) batteries
Double ventilation:
If the control panel has double ventilation, we have two ventilation outputs.
The first ventilation output is VENT1 labeled, and second ventilation level is VENT2 labeled.
The alarm level in this control panels is 200 ppm.
Factory settings are as follows:
Parameter Value
Margins
Ventilation 1 Level:
50 ppm
Fixed
Ventilation 1 Delay:
4 min
Programmable
(1
9 min)
Post-ventilation 1 delay:
4 min
Fixed
Ventilation 2 Level:
100 ppm
Fixed
Ventilation 2 Delay:
0 min
Fixed
Post-ventilation 2 delay:
0 min
Fixed
Alarm Level:
200 ppm
Fixed
Alarm Delay:
0 min
Fixed
Batteries:
Batteries must be wired to the to the battery output on the board on the right side of the panel,
this output is labelled.
Two 12V-batteries series-connected
12V
12V
-
+
-
+
-
Alarm
OFF
[CO]
Ventilation 2
level
Ventilation 1
Delay
Ventilation 1
ON
Ventilation 1
ON
Post-ventilation 1
Delay
Ventilation 1
OFF
Alarm
ON
Alarm
Delay
Tiempo
Alarm
level
Ventilation 2
Delay
Ventilation 2
ON
Ventilation 2
ON
Post-ventilation 2
Delay
Ventilation 2
OFF
Ventilation 1
level