Chapter 5. Diagnostics
175
Single Channel Bank Mode
Use the following procedures to test the D/I Mux III in channel bank mode (and not yet in the T1
network). Select single channel bank operation with local timing, as described in
Chapter 4.
Configuration and Operation.
Refer to Figure 5-6 for the location of the various test jacks on the
Dual Enhanced DSX-1 Interface and Dual CSU Interface.
Figure 5-6. Test Jack Locations
Local and CGA Alarm Response
1. Loop the T1 output of the D/I Mux III T1-1 Transmit to T1-1 Receive with a bantam
cable, or with a loopback connector on the shelf backplane connector (this is the
recommended method for fully testing a shelf). (See Figures 3-8 through 3-11
in
Chapter 3. Installation
for backplane connector locations.) T1 is looped at the Dual
Enhanced DSX-1 Interface (T1 interface) by connecting A OUT to B IN. T1 is looped
on the Dual CSU Interface (CSUIF) by connecting EQ IN to EQ MON. All alarms
should clear (time-out) in approximately 12.5 seconds. Alarms are timed out when all
LEDs on the Line Interface Units (LIUs) are unlit. The alarms time-out when T1
timing and framing are synchronized and operating normally in the D/I Mux III.
2. Break the T1 line either by removing the loopback connector or by removing the
patch cord from the jackfield. On LIU B, the FRM LED and the LOC LED glow red.
After approximately 2.5 seconds, the CGA LED on LIU B illuminates. The system
control terminal screen displays a message indicating Local T1-1 and CGA T1-1 are
in alarm if terminal alarm reporting is turned on. (Other LEDs will also illuminate.)
ACO Switch and Response
1. Press the ACO switch on the Common Control Unit/Multiplexer Control Unit
(CCU/MCU). The CCU/MCU front panel ACO LED illuminates.
Содержание D/I Mux III System
Страница 20: ......
Страница 36: ...Chapter 1 System Overview and Modes of Operation 16 ...
Страница 40: ...Chapter 1 System Overview and Modes of Operation 20 Figure 1 10 Common Control Unit Block Diagram ...
Страница 45: ...Chapter 1 System Overview and Modes of Operation 25 Figure 1 11 AMCU Motherboard Circuit Flow Block Diagram ...
Страница 51: ...Chapter 1 System Overview and Modes of Operation 31 ...
Страница 76: ...Chapter 3 Installation 56 Figure 3 8 Backplane for 8 Slot Voice and Data Shelf F Female M Male P N 91620 308 ...
Страница 77: ...Chapter 3 Installation 57 Figure 3 9 Backplane for 12 Slot Voice and Data Shelf F Female M Male P N 91620 312 ...
Страница 78: ...Chapter 3 Installation 58 Figure 3 10 Backplane for 24 Slot Voice and Data Shelf F Female M Male P N 91620 324 ...
Страница 79: ...Chapter 3 Installation 59 ...
Страница 192: ...Chapter 5 Diagnostics 172 Figure 5 2 DB 15 Male T1 Loopback Connector Figure 5 3 RJ 48 T1 Loopback Connector ...
Страница 227: ...D I Mux III User s Manual Appendix A D I Mux III Specifications APPENDIX A D I MUX III SPECIFICATIONS ...
Страница 232: ...D I Mux III User s Manual Appendix B 24 Volt Systems 212 APPENDIX B 24 VOLT SYSTEMS ...
Страница 234: ...D I Mux III User s Manual Appendix C Accessories Installation APPENDIX C ACCESSORIES INSTALLATION ...
Страница 237: ...D I Mux III User s Manual Appendix D Preconfigured Maps APPENDIX D PRECONFIGURED MAPS ...
Страница 243: ...D I Mux III User s Manual Appendix E SNMP APPENDIX E SNMP ...
Страница 265: ...D I Mux III User s Manual Appendix G Modem Interfaces APPENDIX G MODEM INTERFACES ...
Страница 284: ...D I Mux III User s Manual Appendix H Set Report Options APPENDIX H SET REPORT OPTIONS ...
Страница 327: ...D I Mux III User s Manual Appendix I Traps and Modem Dial Out Configuration 307 Figure J 20 RJ 48 pin out ...