Power + 24 VDC MAX–
The RAD-0102-6 is powered from 12 to 24 Volts
DC. You may use the supplied 12 Volt DC Power Adapter or other 12 to 24
Volt DC Power Source.
•
Power -
Ground
•
B
Back-up battery
•
Battery -
Back-up battery Ground
•
CL01:4-20mA
4-20 mA for CO2: 0 to 50,000ppm
•
GND
4-20mA GND
•
CL02:4-20mA
4-20 mA for Temp: 32 to 122° F (0-50°C)
•
Alarm 1
– is fixed. It cannot be configured. It is set to activate if the
average CO2 Concentration is above 0.5% (5000 ppm) for 8 hours.
•
Relay 2
– is activated by
Alarm
2
.
•
Alarm 2
can be configured to alarm when CO2 Concentration reaches
Alarm 2 Set Point
.
•
Alarm 2
Set Point
can be configured for
0.5% (5000 ppm)
1.0%,1.5%,2.0%,2.5%,3.0%.
•
Relay 3
– is activated by
Alarm 3
.
•
Alarm 3
can be configured to alarm when CO2 Concentration reaches
Alarm 3 Set Point
.
•
Alarm 3 Set Point
can be configured for 2.0%,2.5%,3.0%,3.5%,4.0%.
•
The Peak current for all relays is
2A@30 VDC or 250 VAC
.
•
All relays are Single Pole Double Throw with a Common (
COM
), Normally
Open (
NO
) and Normally Closed (
NC
) contacts.
•
All relays are Single Pole Double Throw.
•
Relays are rated,
2A @ 30 VDC or 250 VAC
.