5. Troubleshooting charts
NO
NO
See "Troubleshooting
the Bus Converter RS-
485 Network"
YES
NO
YES
Is the "Faulted"
sensor plugged into in
this FIB?
YES
YES
NO
Locate the FIB where the
sensor is connected
NO
One or more sensors in
"Fault"
or not reading correctly
Check the "Status"
screen on the
EZSentinel128
or
WS1 Webserver
Are all installed bus
converters online?
Locate the first
bus converter with
faulted sensors
Are errors indicated?
Locate first Field
Interconnect Enclosure
(FIB)
Are both
the red and green
LEDs on in this FIB?
See chart above for error
codes
YES
Unplug and clean the
sensor connector with
99%+ isopropyl alcohol
on both the plug and jack
Is the sensor now
working correctly?
Replace sensor
and assign the new
serial number in WS1 or
EZ128
Error Codes
Bus Converter
WS1 Webserver EZSentinel128
Red LED
Green LED CAT5 Cable
Sensor Cable
Online
Online green
1 sec on/1 sec off
On
Bus converter OK
Offline
Online red
n/a
Off
See "Troubleshooting the RS-485 Netwrok"
Bus Low
Data shorted low
3
n/a
Blue shorted to any white
Green shorted to white or black
Bus High
Data Shorted High
4
n/a
Blue shorted to green, orange or brown
Green shorted to red
Bus overload
Bus power overload
1
n/a
Green, orange or brown shorted to any white
Red shorted to white or black
No sensors
No sensor on bus
2
n/a
Blue open or disconnect switches off
Green open or sensor unplugged
Other faults
Sensor reads 85C or 185F
Green, orange and brown open
Red open