pag
47
Application: Unit for radiant panels
Size
17 21 31
41
51
61
71
81 91 101
121
COOLING
Cooling capacity
1 kW 8,07
8,83
10,5 13,8 17,7 21,9 26,2 29,6 33,6 37,5 42,3
Compressor power input
1 kW 1,42
1,53
1,94
2,33 3,04 3,88 4,81 5,17 5,94 6,87 7,82
Total power input
2 kW 1,43
1,54
1,95
2,34 3,05 3,89 4,82 5,18 5,95 6,88 7,83
EER
kW 5,64 5,73 5,38 5,9 5,80 5,63 5,44 5,71 5,65 5,45 5,4
HEATING
Heat
output
3
kW 6,95 7,5 9,36 12 16,1 19,7 24,7 26,5 31 36,7 41,6
Compressor power input
3 kW 1,28
1,4
1,77
2,27 2,88 3,53 4,47 4,89 5,62 6,41 7,28
Total power input
2 kW 1,29
1,41
1,78
2,28 2,89 3,54 4,48 4,9 5,63 6,42 7,29
COP
kW
5,39
5,32
5,26 5,26 5,57 5,56 5,51 5,41 5,51 5,72 5,71
COMPRESSOR
Type of compressors
SCROLL
No. of Compressors
1
Std Capacity control steps
1
Refrigerant charge (C1)
kg
0,9
0,9
1,1 1,1 1,4 1,6 1,9 2,5 3,2 3,1 3,3
Refrigerant circuits
1
INTERNAL EXCHANGER
Type of internal exchanger 4
PHE
No. of internal exchangers
1
Water flow rate
1 l/s
0,39
0,42
0,5
0,66 0,85 1,05 1,25 1,41 1,61 1,79 2,02
max
Water
flow
rate
l/s 0,64 0,7 0,84 1,1 1,41 1,74 2,09 2,36 2,68 2,99 3,37
Useful pump discharge
head
kPa
46.9 43.1 43.4 28.3 20.4 41.0 33.3 24.3 17.8 83.5 41.8
Water
content
l 0,6 0,6 0,8 0,8 0,9 1,1 2,2 2,5 2,9 2,9 3,2
EXSTERNAL EXCHANGER
type of external exchanger 4
PHE
No. of exsternal exchangers
1
Water flow rate
l/s
0,45
0,49
0,59
0,77 0,99 1,23 1,48 1,66 1,89 2,12 2,39
max Water flow rate
l/s
0,76
0,82
0,99
1,28 1,65 2,05 2,47 2,77 3,15 3,53 3,99
Pressure
drop
kPa
28 31 31 43 49 51 59 52 53 75 80
Connections
Water fittings
5
1"GAS F
EXPANSION VESSEL
Expansion vessel capacity
l
1
2
No. of expansion vessels
1
HYDRAULIC CIRCUIT
Max water side pressure
kPa
550
Safety valve calibration
kPa
600
POWER SUPPLY
Standard power supply
230/1/50
400/3/50+N
Dimensions
Length
mm 402 402 402 402 402 573 573 573 573 573 573
Depth
mm 602 602 602 602 602 604 604 604 604 604 604
Height
mm 785 785 785 785 785 858 858 858 858 858 858
STANDARD UNIT WEIGHTS
Shipping weight
kg 79 81 84 88 96 112 126 143 159 160 166
Operating weight
kg 81 83 86 90 98 115 129 147 163 164 170
(1) data referred to the following conditions :
external exchanger water = 30/35°C
internal exchanger water = 23/18°C
(2) The total absorbed power is obtained adding the compressors absorbed power + the power absorbed by the auxiliary circuit.
(3) data referred to the following conditions :
WATER TO INTERNAL EXCHANGER 40/45°C
External exchanger inlet water = 10°C
The water flow in the external exchanger is the same of the cooling operation.
(4) PHE = plates
(5) water connections both source side and utility side
SETTING THE CUT-OUT DEVICES AND CONTROLS
On
Off
Value
High pressure safety switch
kPa
4200
3300
--
Low pressure safety switch
kPa
200
350
--
Antifreeze protection
°C
4
6,5
Max compressor starts per hour
Nr
--
--
10
Safety discharge thermostat
°C
--
--
120