START-UP 

 

ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES. 

THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF 

THE SYSTEM. 

ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS. 

 

PRELIMINARY CHECKS  

Before checking, please verify the following  
1.  the unit should be installed properly and in conformity 

with this manual. 

2.  the electrical power supply line should be sectioned at 

the beginning. 

3.  the sectioning device is locked and the proper warning 

“not to operate” sign is placed on the handle.  

4.  make sure no tension is present  
5.  the coils must be clean and free of obstacles  
6.  the ventilators must be free of leaves, cardboard, fixed 

obstacles (beams, barriers, etc.), snow, etc  

7.  the external ventilators must not be blocked  

 

The external ventilators can be subject to a temporary 
block, especially if the inactivity period before the first 
start-up was quite long or if external temperature is very 
low. It is also possible to unblock them manually (ONLY 
WHEN THE UNIT IS UNPLUGGED  – RISK OF 
INJURES) so that jams or electric overloads  are 
avoided when the unit is restarted.  

REFRIGERANT SYSTEM 

Carefully check the refrigerating circuit: the presence of oil 
stains can mean leakage caused by transportation, 
movements or other). 
Open the cocks of the refrigerator circuit, if there are any. 
Using the unit manometers, if present, or service 
manometers, verify that the refrigerating circuit is in 
pressure. 
Make sure that all the service outlets are closed with proper 
caps; if caps are not present a leak of refrigerant can be 
possible.

 

WATER SYSTEM 

Ensure that the plumbing system has been washed. Drain 
the wash water before connecting the unit to the system. 
Check that the water circuit has been filled and pressurised. 
Accertarsi che non siano presenti perdite . 
Check that the shut-off valves in the circuit are in the 
"OPEN" position.  
Check that there is no air in the circuit. If required, bleed it 
using the vent valves in the system. 
When using antifreeze solutions, make sure the glycol 
percentage is suitable for the type of use envisaged.  
% weight of ethylene 
glycol 

10 % 

20 % 

30 % 

40 % 

Freezing point 

- 4 °C 

- 9 °C 

- 15 °C  - 23 °C 

Safety temperature 

- 2 °C 

- 7 °C 

- 13 °C  - 21 °C 

 
Check that the circulator pumps are not blocked. In fact, 
their motor shaft may seize up, especially after long 
shutdowns. Unblocking can be accomplished with a 
screwdriver using the purge hole.  

ELECTRICAL SYSTEM 

Check the proper tightening of the screws that fix the 
conductors to the electrical components in the board 
(during handling and transportation, the vibrations could 
have loosened them). 
Verify that the unit is connected to the ground plant.  
Control that all panels and protection devices of the unit are 
repositioned and blocked. 
Charge the unit by closing the sectioning device, but leave 
it on OFF. 
Make sure that the tension and net frequency values are 
within the limit of: 
230 +/- 6% single phase unit; 400/3/50 +/- 6% three-phase 
unit 
Control the unbalancing of the phases: it must be lower 
than 2% . 
Example:  
L1 - L2 = 388 V,    L2 - L3 = 379 V,   L3 - L1 = 377 V   
average of the measured values = (388 + 379 + 377) / 3 = 
381 
maximum deviation from the average = 388-381= 7V 
Unbalancing = (7/381) x 100 = 1.83%  = ACCEPTABLE 
Operating out of the indicated limits causes the loss of the 
guarantee as well as very serious damages.  

IF THE CRANKCASE HEATERS ARE FITTED 

when the unit is started up for the first time and following all 
prolonged periods of inactivity is OBLIGATORY to connect 
the oil heaters on the compressor crankcase at least 8 
hours before the compressor is to be starter. 
BEFORE POWERING THE HEATERS, OPEN THE 
COMPRESSORS COCKS, IF PRESENT. 
To supply the heaters is necessary to switch off the isolator 
switch on the unit. 
To make sure  that hte heaters are working, check the 
power input with amperometic pliers. 
At start-up the compressor cranckase temperature on the 
lower side must be higher at least of  10°C than the 
external temperature. 
DO NOT START THE COMPRESSOR WITH THE 
CRANKCASE OIL BELOW OPERATING TEMPERATURE.  

 
 

 

Содержание WSHN-EE 101

Страница 1: ...TER M03S40F6 HN R TO WA 6 11 EE 71 ATER HE CIRCUI Instal 17 81 AT PUM IT FOR IN llation 7 21 91 P REVER NDOOR n and U 31 101 RSIBLE O INSTALL Use M 41 5 12 ON THE LATION anual 51 6 1 REFRIG 61 GERANT...

Страница 2: ......

Страница 3: ...NNECTION TO THE MAINS 20 SYSTEM COMPOSITION 20 FUNCTIONAL CONNECTIONS 21 S T A R T U P 2 9 PRELIMINARY CHECKS 29 REFRIGERANT SYSTEM 29 WATER SYSTEM 29 ELECTRICAL SYSTEM 29 VERIFy tensions absorptions...

Страница 4: ...UMBER This provides unique identification of the machine It makes it possible to trace the specific features of the unit and to identify the components installed in it Without this number it is not po...

Страница 5: ...robes from a depth of 30 to 100 m 6 groundwater collector disposal wells 7 When it cools the refrigerant becomes liquid 8 The expansion valve causes a sudden drop in the pressure of the refrigerant wh...

Страница 6: ...r either towards the sanitary hot water storage or towards the heating equipment 3 sanitary hot water storage 4 fan coil heating 5 if the room needs to be heated the 3 way valve diverts the water towa...

Страница 7: ...ining the system at a safety temperature in WINTER MAINTENANCE function Put the unit in OFF parameter 45 must be 1 yellow led is flashing Minimize the consumptions maintaining the system at a safety t...

Страница 8: ...Control parameter 29 Modify the water temp in MAINTENANCE heating Control parameter parametro 43 Modify the water temp in MAINTENANCE cooling Control parameter 42 COMMON CAUSES OF SHUTDOWN 1 set poin...

Страница 9: ...r and glycol mix for air conditioning within the limits defined in the technical bulletin and this manual Any use other than that specified does not imply any commitment or constraint by the manufactu...

Страница 10: ...RISKS A smell of burning smoke or other indications of serious irregularity could signal the onset of situations liable to cause damage to persons or property or to the unit itself Isolate the unit fr...

Страница 11: ...FRIG 8 Product R 410A Identification of the supplier See heading or bottom of page No of emergency telephone See heading or bottom of page 02 Composition information on ingredients Substance Compound...

Страница 12: ...e driver compartment Verify that the driver is informed on the potential risk of the load and that he knows what to do in case of an accident or emergency Before starting the transport verify that the...

Страница 13: ...the circuits can assume values which activate the safety valves HANDLING The operation of handling the unit must be carried out respecting the instructions of the safety norms in force Legislative Dec...

Страница 14: ...e only to qualified and authorized personnel 2 SAFETY VALVE only if present on the unit the installer is responsible for evaluating the opportunity of installing drain tubes in conformity with the loc...

Страница 15: ...ubes with heating cables under the tubes insulation empty the system by verifying that o no taps are closed so they can not trap the water even after emptying o there are no low points where the water...

Страница 16: ...in the event of the following the water in the system is very low the unit will not be used in a private house in an industrial process or other USE SCHEMA 1 Heating integration 2 3 ways ON OFF sanit...

Страница 17: ...FLOW RATE This makes it possible to limit water consumption increase energy efficiency and extend the unit s operating limits It can be modified by using 1 Modulating motorized valve 2 Cut off valve 3...

Страница 18: ...the ELECTRICAL CONNECTIONS section double temperature underfloor heating manages the elements of a mixed system with underfloor piping fan coil radiators circulator mixer valve outlet probe see detai...

Страница 19: ...should be determined according to the plant features The section of supply cables and protection cable must be seized according to the characteristics of the protections used SIGNALS DATA LINES Do no...

Страница 20: ...heck the shipping document descriptions USER AMBIENT TERMINAL Permits setting the unit function modes cooling heating ECO and to display the alarms ELECTRIC REFRIGERATOR WATER This is standard on cert...

Страница 21: ...SET POINT COMPENSATION with 4 20 mA signal 12 interface via RS485 1 ON OFF FROM REMOTE CONTROL Generally the unit is delivered with bridged terminals if the control is not used the bridge should not...

Страница 22: ...ower than par 180 1 1 MAIN ADJUSTMENT UNIT IN HEATING MODE in heat pump mode the compressor is disabled 2 1 POWER LIMITATION ACCORDING TO EXTERNAL TEMPERATURE the following behaviour occurs as the ext...

Страница 23: ...in case of unit shutdown MAINTENANCE With the unit coupled to a boiler the maintenance function if enabled activates the boiler instead of the heat pump if necessary The diagram on the side is indicat...

Страница 24: ...COND SET POINT it is necessary to set par 50 2 In this mode the inputs on the main card will be configured as follows CN1_10 11 sanitary hot water request CN1_14 16 second set point Refer to the wirin...

Страница 25: ...ear its operation limits curve B in the graph the compensation must be enabled during start up PARAMETERS INDICATIVE VALUES par Description Meaning value 12 CextMaxH Ext Temp max winter correction 15...

Страница 26: ...anels can be managed in three ways 1 the valve is managed to maintain the outlet temperature at par 192 value independently of the unit operating mode COOLING or HEATING 2 calculated automatically in...

Страница 27: ...HEATING 11 SET POINT COMPENSATION ON THE TEMPERATURE OR EXTERNAL ENTHALPY Optimises unit energy efficiency by automatically adjusting the set point according to enthalpy or the external temperature R...

Страница 28: ...s twisted and shielded Section of conductor 0 22mm2 0 35mm 2 Nominal capacity between conductors 50 pF m nominal impedance 120 Recommended cable BELDEN 3105 A TYPE OF NETWORK The serial lines must be...

Страница 29: ...eck that there is no air in the circuit If required bleed it using the vent valves in the system When using antifreeze solutions make sure the glycol percentage is suitable for the type of use envisag...

Страница 30: ...te L h The cooling power is shown in the TABLE ON GENERAL TECHNICAL DATA included in this manual referred to specific air water conditions or in the tables on cooling PERFORMANCE IN THE TECHNICAL BULL...

Страница 31: ...ION The thermoregulation is based on the OUTLET temperature The unit is dimensioned for a determined TOTAL HEAD between input and output water temperature Usually the project step is 5 C if the value...

Страница 32: ...tatus 1 static set point The static set point can so be modified in a dynamic way by two CORRECTIONS based on as many unit external factors correction based on the ext temp enthalpy correction based o...

Страница 33: ...rculation pump measures the water temperature and activates the compressor if required to take the water temperature to the set point level Summer maintenance set point par 42 Winter maintenance set p...

Страница 34: ...erating mode leds remain alight even when the machine is in the maintenance status The maintenance set points if activated control the water temperature when the unit is OFF or on STANDBY To do this t...

Страница 35: ...faulty Allarme serial faulty Allarme serial faulty FUNCTIONING TEST The Test key allows the verification of the proper functioning of the all six signalisation LEDs When it is pressed all leds are ON...

Страница 36: ...Point C 2 Temperature drop in degrees centigrade given by the compressor including compensations if any C 3 Resource activation timer When this value reaches the value fixed at the next status TimeSc...

Страница 37: ...e repeated resetting could cause irreversible damage To avoid this the unit can only be reset MANUALLY from the keyboard only when the cause for the alarm has been removed PRE ALARMS and SIGNALS warn...

Страница 38: ...w Auto E 18 System charged with water MANUAL E 19 Phase monitor Auto E 20 Antifreeze alarm MANUAL C 21 Antifreeze PREAlarm Auto C 22 High pressure PreAlarm Auto C 24 Pump change Auto E 25 flow alarm C...

Страница 39: ...re this problem may occur Check that the panelling is fastened correctly Poor fastening may give rise to malfunctions and abnormal noise and vibration MAINTENANCE INSPECTIONS Foresee inspection assist...

Страница 40: ...or cooling units or when seasonal switching should be performed When restarting refer to the SWITCHING ON section Schedule technical assistance in advance to avoid hitches and be able to use the insta...

Страница 41: ...0 8 69 16 0 44 28 60 46 43 78 38 84 26 01 5 2 6 92 22 65 8 79 2 73 7 73 16 2 44 77 60 95 44 24 39 32 26 46 5 4 7 96 23 70 9 77 3 73 6 79 16 4 45 26 61 44 44 69 39 79 26 90 5 6 8 97 24 73 10 72 4 71 5...

Страница 42: ...85 45 47 37 6 82 67 98 58 78 62 76 01 60 26 26 8 66 37 82 56 64 07 60 18 45 77 37 8 82 94 98 84 78 86 76 27 60 50 27 0 66 71 82 90 64 38 60 51 46 08 38 0 83 20 99 09 79 09 76 53 60 73 27 2 67 05 83 2...

Страница 43: ...ded or included other uses are isolated etc 4 Dirt water filter valves open air bubbles in the plant 5 dirty exchanger 6 Manostat transducer loose electric contacts terminals wiring cables interrupted...

Страница 44: ...irt pin blocked mechanically LOW PRESSURE heating 1 low water temperature see operating limits 2 insufficient water flow to the exchanger high thermal difference between input and output 3 not CONSTAN...

Страница 45: ...ored in special containers When recovering the substances present in the unit all measures must be taken to avoid damaging persons and things and polluting the surrounding area Awaiting dismantling an...

Страница 46: ...9 5 44 4 155 134 Water content l 0 6 0 6 0 8 0 8 0 9 1 1 2 2 2 5 2 9 2 9 3 2 EXSTERNAL EXCHANGER Type of internal exchanger 4 PHE No of internal exchangers 1 Water flow rate Internal Exchanger 1 l s 0...

Страница 47: ...al exchangers 1 Water flow rate l s 0 45 0 49 0 59 0 77 0 99 1 23 1 48 1 66 1 89 2 12 2 39 max Water flow rate l s 0 76 0 82 0 99 1 28 1 65 2 05 2 47 2 77 3 15 3 53 3 99 Pressure drop kPa 28 31 31 43...

Страница 48: ...certification The sound pressure is measured at 1 m from the external surface of the unit in open field conditions data referred to the following conditions internal exchanger water 12 7 C external ex...

Страница 49: ...OPTIONAL 14 3 WAYS VALVE OPTIONAL 15 CLEARANCE ACCESS RECOMMENDED 16 POWER INPUT 17 1 2 GAS CHARGE FITTING G BARYCENTRE M mm 193 190 195 193 176 N mm 173 173 173 170 187 O mm 169 170 172 168 171 P mm...

Страница 50: ...NDED 16 POWER INPUT 17 19 1 2 GAS CHARGE FITTING SIZES 61 71 81 91 18 19 1 2 GAS CHARGE FITTING SIZES 101 121 G BARYCENTRE M mm 154 167 178 185 187 189 N mm 213 200 191 182 180 178 O mm 286 300 330 33...

Страница 51: ......

Страница 52: ...info clivet es CLIVET UK LTD Fareham Hampshire U K Tel 44 0 1489 572238 Fax 44 0 1489 573033 info clivet uk co uk CLIVET NEDERLAND B V Amersfoort Netherlands Tel 31 0 33 7503420 Fax 31 0 33 7503424 in...

Отзывы: