WATER CONNECTIONS

 

 

GENERAL 

Piping must be designed with the least possible number of 
bends and head variations. If the pressure chute of the 
installation is above the useful prevalence of the pump, the 
water delivery capacity is reduced as well as, as a 
consequence, the thermal exchange and the yield.  

INTERCEPTING VALVES 

Install on the input and output of the user parts 
(exchangers, coils, humidifiers, etc) So that it will be 
possible to carry out all the service operations and possible 
substitutions without emptying the installation. 

PRESSURE AND TEMPERATURE INDICATOR 

Install on the input and output of the user parts 
(exchangers, coils, humidifiers, etc) So that it will be 
possible to carry out all the service operations. 

AUTOMATIC OR MANUAL ESCAPE VALVES 

Install the highest points of tubes in a way that the air can 
escape form the circuit.  

BLEEDING COCK 

Install them at the lowest points of the circuit, so as to allow 
emptying. 

LEAKAGE TESTS 

Before performing the insulation of the tubes, carry out a 
leakage test. 

TUBE INSULATION  

All tubes of water must be insulated so that to avoid the 
formation of condensation and thermal dispersions along 
the tubes themselves. Verify that the insulation is the 
vapour coil type. The connections for the air escape and for 
the emptying must be out of the insulating thickness to 
assure the accessibilità. 

CONNECTIONS SUPPORTS 

The weight of the hydraulic connections must be supported 
in the exterior of the unit so as not to stress the connections 
of user devices (exchangers, coils, humidifiers, etc ) . 

ANTI-VIBRATION DEVICES 

In case of units with anti-vibration devices, it is necessary to 
assemble elastic joints, even on water connections. 

RISK OF FREEZE 

If the unit and the relevant water connections are subject to 
temperatures near 0°C:  

 

mix the water of the system with glycol 

  protect the tubes with heating cables under the tubes 

insulation 

 

empty the system by verifying that: 

o

  no taps are closed so they can not trap the water, 

even after emptying 

o

  there are no low points where the water can 

stagnate even after emptying; blow if necessary 

INTALLATION EMPTYING  

The refilling of the water present in the installation increase 
the oxidation phenomena and lime deposits.  
If necessary empty only the interested system section and 
anyway empty or refill the installation if necessary .  

EXPANSION TANK 

The installation must be kept at the right pressure by both 
an expansion tank and a combined valve of pressure 
reduction and discharge; if the components are present on 
the unit, they must be installed on the installation. The 
expansion tank must be dimensioned in function of the 
water in the installation. 

 

EXCHANGER USE SIDE 

 

FILTER 

It is very important for the water to be free of impurities. If it 
is not, the efficiency of thermal exchange is diminished. In 
worst cases, the exchanger can be irreparably damaged. If 
the filter is not present on the machine, it must be 
immediately installed upstream from the unit, in a position 
which can be easily reached for cleaning 

FLOW SWITCH 

The flow switch must be present as a component of the 
system, so as to ensure shutdown of the unit if water is not 
circulating. It must be installed in a straight tract of the 
tubes, not near the elbows, which can generate harmful 
turbulence. 

UNFREEZABLE LIQUIDS 

If the unit is used when the water temperature is lower than 
+ 4°C, avoid the formation of ice by using unfreezable 
liquids (ex. Ethilenic Glycol) in the necessary percentage. 
The use must also be determined for room temperatures 
near 0°C . 

ANTIFREEZE HEATERS  

If the unit is equipped with antifreeze heaters on the 
exchanger side (standard or optional according to the 
models), verify that they are electrically fed during periods 
that the machine is stopped (night, weekends, long stops) 

WASHING THE SYSTEM 

Carefully wash the system by using clean water and 
discharge it before connecting the unit. 

 

Содержание WSHN-EE 101

Страница 1: ...TER M03S40F6 HN R TO WA 6 11 EE 71 ATER HE CIRCUI Instal 17 81 AT PUM IT FOR IN llation 7 21 91 P REVER NDOOR n and U 31 101 RSIBLE O INSTALL Use M 41 5 12 ON THE LATION anual 51 6 1 REFRIG 61 GERANT...

Страница 2: ......

Страница 3: ...NNECTION TO THE MAINS 20 SYSTEM COMPOSITION 20 FUNCTIONAL CONNECTIONS 21 S T A R T U P 2 9 PRELIMINARY CHECKS 29 REFRIGERANT SYSTEM 29 WATER SYSTEM 29 ELECTRICAL SYSTEM 29 VERIFy tensions absorptions...

Страница 4: ...UMBER This provides unique identification of the machine It makes it possible to trace the specific features of the unit and to identify the components installed in it Without this number it is not po...

Страница 5: ...robes from a depth of 30 to 100 m 6 groundwater collector disposal wells 7 When it cools the refrigerant becomes liquid 8 The expansion valve causes a sudden drop in the pressure of the refrigerant wh...

Страница 6: ...r either towards the sanitary hot water storage or towards the heating equipment 3 sanitary hot water storage 4 fan coil heating 5 if the room needs to be heated the 3 way valve diverts the water towa...

Страница 7: ...ining the system at a safety temperature in WINTER MAINTENANCE function Put the unit in OFF parameter 45 must be 1 yellow led is flashing Minimize the consumptions maintaining the system at a safety t...

Страница 8: ...Control parameter 29 Modify the water temp in MAINTENANCE heating Control parameter parametro 43 Modify the water temp in MAINTENANCE cooling Control parameter 42 COMMON CAUSES OF SHUTDOWN 1 set poin...

Страница 9: ...r and glycol mix for air conditioning within the limits defined in the technical bulletin and this manual Any use other than that specified does not imply any commitment or constraint by the manufactu...

Страница 10: ...RISKS A smell of burning smoke or other indications of serious irregularity could signal the onset of situations liable to cause damage to persons or property or to the unit itself Isolate the unit fr...

Страница 11: ...FRIG 8 Product R 410A Identification of the supplier See heading or bottom of page No of emergency telephone See heading or bottom of page 02 Composition information on ingredients Substance Compound...

Страница 12: ...e driver compartment Verify that the driver is informed on the potential risk of the load and that he knows what to do in case of an accident or emergency Before starting the transport verify that the...

Страница 13: ...the circuits can assume values which activate the safety valves HANDLING The operation of handling the unit must be carried out respecting the instructions of the safety norms in force Legislative Dec...

Страница 14: ...e only to qualified and authorized personnel 2 SAFETY VALVE only if present on the unit the installer is responsible for evaluating the opportunity of installing drain tubes in conformity with the loc...

Страница 15: ...ubes with heating cables under the tubes insulation empty the system by verifying that o no taps are closed so they can not trap the water even after emptying o there are no low points where the water...

Страница 16: ...in the event of the following the water in the system is very low the unit will not be used in a private house in an industrial process or other USE SCHEMA 1 Heating integration 2 3 ways ON OFF sanit...

Страница 17: ...FLOW RATE This makes it possible to limit water consumption increase energy efficiency and extend the unit s operating limits It can be modified by using 1 Modulating motorized valve 2 Cut off valve 3...

Страница 18: ...the ELECTRICAL CONNECTIONS section double temperature underfloor heating manages the elements of a mixed system with underfloor piping fan coil radiators circulator mixer valve outlet probe see detai...

Страница 19: ...should be determined according to the plant features The section of supply cables and protection cable must be seized according to the characteristics of the protections used SIGNALS DATA LINES Do no...

Страница 20: ...heck the shipping document descriptions USER AMBIENT TERMINAL Permits setting the unit function modes cooling heating ECO and to display the alarms ELECTRIC REFRIGERATOR WATER This is standard on cert...

Страница 21: ...SET POINT COMPENSATION with 4 20 mA signal 12 interface via RS485 1 ON OFF FROM REMOTE CONTROL Generally the unit is delivered with bridged terminals if the control is not used the bridge should not...

Страница 22: ...ower than par 180 1 1 MAIN ADJUSTMENT UNIT IN HEATING MODE in heat pump mode the compressor is disabled 2 1 POWER LIMITATION ACCORDING TO EXTERNAL TEMPERATURE the following behaviour occurs as the ext...

Страница 23: ...in case of unit shutdown MAINTENANCE With the unit coupled to a boiler the maintenance function if enabled activates the boiler instead of the heat pump if necessary The diagram on the side is indicat...

Страница 24: ...COND SET POINT it is necessary to set par 50 2 In this mode the inputs on the main card will be configured as follows CN1_10 11 sanitary hot water request CN1_14 16 second set point Refer to the wirin...

Страница 25: ...ear its operation limits curve B in the graph the compensation must be enabled during start up PARAMETERS INDICATIVE VALUES par Description Meaning value 12 CextMaxH Ext Temp max winter correction 15...

Страница 26: ...anels can be managed in three ways 1 the valve is managed to maintain the outlet temperature at par 192 value independently of the unit operating mode COOLING or HEATING 2 calculated automatically in...

Страница 27: ...HEATING 11 SET POINT COMPENSATION ON THE TEMPERATURE OR EXTERNAL ENTHALPY Optimises unit energy efficiency by automatically adjusting the set point according to enthalpy or the external temperature R...

Страница 28: ...s twisted and shielded Section of conductor 0 22mm2 0 35mm 2 Nominal capacity between conductors 50 pF m nominal impedance 120 Recommended cable BELDEN 3105 A TYPE OF NETWORK The serial lines must be...

Страница 29: ...eck that there is no air in the circuit If required bleed it using the vent valves in the system When using antifreeze solutions make sure the glycol percentage is suitable for the type of use envisag...

Страница 30: ...te L h The cooling power is shown in the TABLE ON GENERAL TECHNICAL DATA included in this manual referred to specific air water conditions or in the tables on cooling PERFORMANCE IN THE TECHNICAL BULL...

Страница 31: ...ION The thermoregulation is based on the OUTLET temperature The unit is dimensioned for a determined TOTAL HEAD between input and output water temperature Usually the project step is 5 C if the value...

Страница 32: ...tatus 1 static set point The static set point can so be modified in a dynamic way by two CORRECTIONS based on as many unit external factors correction based on the ext temp enthalpy correction based o...

Страница 33: ...rculation pump measures the water temperature and activates the compressor if required to take the water temperature to the set point level Summer maintenance set point par 42 Winter maintenance set p...

Страница 34: ...erating mode leds remain alight even when the machine is in the maintenance status The maintenance set points if activated control the water temperature when the unit is OFF or on STANDBY To do this t...

Страница 35: ...faulty Allarme serial faulty Allarme serial faulty FUNCTIONING TEST The Test key allows the verification of the proper functioning of the all six signalisation LEDs When it is pressed all leds are ON...

Страница 36: ...Point C 2 Temperature drop in degrees centigrade given by the compressor including compensations if any C 3 Resource activation timer When this value reaches the value fixed at the next status TimeSc...

Страница 37: ...e repeated resetting could cause irreversible damage To avoid this the unit can only be reset MANUALLY from the keyboard only when the cause for the alarm has been removed PRE ALARMS and SIGNALS warn...

Страница 38: ...w Auto E 18 System charged with water MANUAL E 19 Phase monitor Auto E 20 Antifreeze alarm MANUAL C 21 Antifreeze PREAlarm Auto C 22 High pressure PreAlarm Auto C 24 Pump change Auto E 25 flow alarm C...

Страница 39: ...re this problem may occur Check that the panelling is fastened correctly Poor fastening may give rise to malfunctions and abnormal noise and vibration MAINTENANCE INSPECTIONS Foresee inspection assist...

Страница 40: ...or cooling units or when seasonal switching should be performed When restarting refer to the SWITCHING ON section Schedule technical assistance in advance to avoid hitches and be able to use the insta...

Страница 41: ...0 8 69 16 0 44 28 60 46 43 78 38 84 26 01 5 2 6 92 22 65 8 79 2 73 7 73 16 2 44 77 60 95 44 24 39 32 26 46 5 4 7 96 23 70 9 77 3 73 6 79 16 4 45 26 61 44 44 69 39 79 26 90 5 6 8 97 24 73 10 72 4 71 5...

Страница 42: ...85 45 47 37 6 82 67 98 58 78 62 76 01 60 26 26 8 66 37 82 56 64 07 60 18 45 77 37 8 82 94 98 84 78 86 76 27 60 50 27 0 66 71 82 90 64 38 60 51 46 08 38 0 83 20 99 09 79 09 76 53 60 73 27 2 67 05 83 2...

Страница 43: ...ded or included other uses are isolated etc 4 Dirt water filter valves open air bubbles in the plant 5 dirty exchanger 6 Manostat transducer loose electric contacts terminals wiring cables interrupted...

Страница 44: ...irt pin blocked mechanically LOW PRESSURE heating 1 low water temperature see operating limits 2 insufficient water flow to the exchanger high thermal difference between input and output 3 not CONSTAN...

Страница 45: ...ored in special containers When recovering the substances present in the unit all measures must be taken to avoid damaging persons and things and polluting the surrounding area Awaiting dismantling an...

Страница 46: ...9 5 44 4 155 134 Water content l 0 6 0 6 0 8 0 8 0 9 1 1 2 2 2 5 2 9 2 9 3 2 EXSTERNAL EXCHANGER Type of internal exchanger 4 PHE No of internal exchangers 1 Water flow rate Internal Exchanger 1 l s 0...

Страница 47: ...al exchangers 1 Water flow rate l s 0 45 0 49 0 59 0 77 0 99 1 23 1 48 1 66 1 89 2 12 2 39 max Water flow rate l s 0 76 0 82 0 99 1 28 1 65 2 05 2 47 2 77 3 15 3 53 3 99 Pressure drop kPa 28 31 31 43...

Страница 48: ...certification The sound pressure is measured at 1 m from the external surface of the unit in open field conditions data referred to the following conditions internal exchanger water 12 7 C external ex...

Страница 49: ...OPTIONAL 14 3 WAYS VALVE OPTIONAL 15 CLEARANCE ACCESS RECOMMENDED 16 POWER INPUT 17 1 2 GAS CHARGE FITTING G BARYCENTRE M mm 193 190 195 193 176 N mm 173 173 173 170 187 O mm 169 170 172 168 171 P mm...

Страница 50: ...NDED 16 POWER INPUT 17 19 1 2 GAS CHARGE FITTING SIZES 61 71 81 91 18 19 1 2 GAS CHARGE FITTING SIZES 101 121 G BARYCENTRE M mm 154 167 178 185 187 189 N mm 213 200 191 182 180 178 O mm 286 300 330 33...

Страница 51: ......

Страница 52: ...info clivet es CLIVET UK LTD Fareham Hampshire U K Tel 44 0 1489 572238 Fax 44 0 1489 573033 info clivet uk co uk CLIVET NEDERLAND B V Amersfoort Netherlands Tel 31 0 33 7503420 Fax 31 0 33 7503424 in...

Отзывы: