44
9 - TECHNICAL INFORMATION
20
25
30
35
40
45
50
55
60
65
70
75
80
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
Q [l/s]
Δ
P [
k
Pa
]
A B C
D
E
F
H
I
J
G
A = 65D-70D
B = 75D
C = 80D
D = 85D
E = 90D-100D
F = 110D
G = 115D
H = 120D
I = 135E
J = 150F-165F-180F
EXCHANGER PRESSURE DROP PARTIAL ENERGY RECOVERY
EXCHANGER PRESSURE DROP TOTAL ENERGY RECOVERY
10
15
20
25
30
35
40
45
50
2
3
4
5
6
7
8
9
10
Q [l/s]
Δ
P [
k
P
a
]
A
A = 65D
B = 70D-75D-80D
C = 115D-120D
D = 135E
E = 85D
F = 150F
G = 165F
H = 90D-100D-180F
I = 110D
B
C
D
E F
G
H
I
CORRECTION FACTOR FOR ANTIFREEZE SOLUTIONS
Q = water flow
dP = pressure drop
Q = water flow
dP = pressure drop
Internal exchanger (evaporator)
5%
10%
15%
20%
25%
30%
35%
40%
Freezing temperature
°C -2,0 -3,9 -6,5 -8,9 -11,8 -15,6 -19,0 -23,4
Safety temperature
°C 3,0 1,0 -1,0 -4,0 -6,0 -10,0 -14,0 -19,0
Cooling Capacity Factor
Nr 0,995 0,990 0,985 0,981 0,977 0,974 0,971 0,968
Compressor input Factor
Nr 0,997 0,993 0,990 0,988 0,986 0,984 0,982 0,981
Internal exchanger Glycol solution flow Factor
Nr 1,003 1,010 1,020 1,033 1,050 1,072 1,095 1,124
Pressure drop Factor
Nr 1,029 1,060 1,090 1,118 1,149 1,182 1,211 1,243
% ethylene glycol by weight
The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchangers in the water circuit during inactivity in winter.
External exchanger (condenser)
5%
10%
15%
20%
25%
30%
35%
40%
Freezing temperature
°C
-2,0 -3,9 -6,5 -8,9 -11,8 -15,6 -19,0
-23,4
Safety temperature *
°C 3,0 1,0 -1,0 -4,0 -6,0 -10,0 -14,0 -19,0
Cooling Capacity Factor
Nr 0,995 0,990 0,985 0,981 0,977 0,974 0,971 0,968
Compressor input Factor
Nr 0,997 0,993 0,990 0,988 0,986 0,984 0,982 0,981
Internal exchanger Glycol solution flow Factor
Nr 1,003 1,010 1,020 1,033 1,050 1,072 1,095 1,124
Pressure drop Factor
Nr 1,029 1,060 1,090 1,118 1,149 1,182 1,211 1,243
% ethylene glycol by weight
The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchangers in the water circuit during inactivity in winter.
* MAX. REDUCTION EXTERNAL EXCHANGER INLET WATER TEMPERATURE
Содержание WSH 100D
Страница 9: ...9 4 WATER CONNECTIONS...
Страница 12: ...12 WATER CONNECTIONS...
Страница 14: ...14 5 ELECTRICAL CONNECTIONS 5 6 CONNECTIONS PERFORMER BY CUSTOMER...
Страница 15: ...15 5 ELECTRICAL CONNECTIONS...
Страница 16: ...16 5 ELECTRICAL CONNECTIONS...
Страница 31: ...31 8 MAINTENANCE...
Страница 46: ...46 NOTE...
Страница 47: ...47...