5 - ELECTRICAL CONNECTIONS
E.1 - RECOGNITION OF THE COMPONENTS FOR
NETWORK
OPERATION
1. password -> Maintenance man (115)
2. configuration -> keypad -> setup -> Id10 = 1,
Id11 = 2 ; only afterwards Id3 = 1
3. configuration -> system -> autoconfiguration -> set Max
Address = 54
HID-H1 starts to find among the first 54 addresses the
devices connected in that moment, then it will detect the
heat pump and the mixing module.
In case of anomaly check the addressing and the bus
connection.
4.
configuration -> system -> list of unit -> it appears the list
of units seen from the system ,
If one of the connected module is not present, check
ardesse, connections and do again the auto-configuration
.
E.2 - RADIANT PANEL CONFIGURATION
1. configuration -> Radiant panels
•
EnVMiscelatrice:
Enable
•
CompAmbHeatEn
: ambient compensation enabling in
heating
•
CompAmbCoolEn
: ambient compensation enabling in
cooling
•
EnCompRugiada
: enables the dew compensation
•
EnModofreddo
: 0=module operating only in heating, 1
cooling only, 2=always
•
SetHeatRadiante
= panel water set-point in heat
•
SetCoolRadiante
=panel water set-point in cool
•
H1H
=max. compensated water temp. in heat
•
H2H
= min. compensated water temp. in heat
•
T1minH
= min. fresh air temp. (corresponding to H1H)
•
T2MaxH
= max. fresh air temp. (corresponding to H2H)
•
H2C
= min. compensated water temp. in cool
•
H1C
= max. compensated water temp. in cool
•
T1MinC
= min. fresh air temp (corresponding to H1C)
•
T2MaxC
= max. fresh air temp. (corresponding to H2C)
•
EnCompText
=0=compensation never active, 1=active
only in cool, 2=active only in heat, 3=always active.
E.3 - CONFIGURATION OF THE ZONE WHERE
HID-H1
IS
INSTALLED
1.
configuration -> zones -> night zone ->
summer eco
setting:
•
setpoint = 27 °C
•
set type= free
•
on type = free
•
Party = enable
•
UR% = 55%
•
Radiant=enable
•
Energy save = disable
2. Repeat the operation for the settings :
•
Summer Comfort ,
•
Winter Eco ,
•
Winter Comfort
Set for each one the appropriate set-point such as:
•
Summer comfort =26°C, UR%=55%,
•
Winter Eco 18°C, UR%=45%,
•
Winter comfort =21°C, UR%=45%.
For each of these modalities it is also possible to decide to
use or not the radiant panels (radiant=enable/disable) in each
single setting.
E.4 - TIME SCHEDULING
1. Select the operating programs of the night zone, for each
day of the week, choosing among the 7 operating
programs.
Schedulings-> zones -> weekly -> night zone
Monday
: Progr. 1 ;
Tuesday
: Progr. 1 ;
Sunday
: Progr. 3
E.5 - PROGRAM PERSONALIZATION
It is possible to modifiy the daily trend of the programs.
Schedulings-> zones -> programs ->
The unit is activated only in COMFORT or ECO MODE.
The demand is effected by the room thermostat according to
the ambient temperature and to the setpoint.
The setpoint is the same of the one of the settings of point
E.3 ; it is possible to modify the value rotating the central but-
ton from the initial display.