5 - ELECTRICAL CONNECTIONS
EXAMPLE OF CONFIGURATION UNIT + DHW MODULE
Operation sequence:
With built-in keyboard:
1.
UNIT CONFIGURATION menu (password required)
2.
set the par 12 = 1
3.
set the par 25 = 1
4.
Only if the valve is provided by the customer: par 358 = see valve datasheet
With keyboard in ambient:
1.
put keyboard in "system’s manager" mode
2.
KEYPAD-CONFIGURATIONS menu (pag 46)
3.
set the par 10 = 1
4.
par 11 = 1
5.
par 2 = 2
6.
CONFIGURATION - SYSTEM - AUTOCONFIGURATION menu
7.
Set "maxaddress = 5"
8.
Wait the system components detection
9.
SYSTEM-CONFIGURATION - UNIT LIST menu
10.
It appears a list of the units viewed from the system
Содержание WSAR-MT-E