5.13 BOILER - OPTION
The unit can be automatically deactivated when the outside
temperature increases under the threshold (p479) ; to replace
it the boiler is activated.
The functionality is active if the unit is in heating operating.
For the boiler management an appropriate kit is available.
Configuration paramenters *
13
Enables boiler fuHeat pump
0 = No; 1 = Always ; 2= No DHW
477
Water return temperature over it the heat pump is
disabled for the safety. Closed valves on heat pump side
478
Hysteresis for heat pump enabling and boiler deactivation
(Open valves on heat pump side)
479
Outside temp. threshold: under it the boiler is enabled
480
Hysteresis of outside temperature for heat pump
reactivation
*
Parameters accessible through the installer password 115).
The access by pwd is reserved to qualified personnel;
The parameters changes may cause malfunctions.
5 - ELECTRICAL CONNECTIONS
This option is not compatible with Master Slave
This option is not compatible with the Electric heaters function
If a circuit breaker is not present the BT6 probe must feel
moving water.
To prevent the heat pump remains disabled after the boiler
stop set the maximum temperature of the boiler to a value
lower than par 477.
It is possible to pilote the electrical resistances:
•
in integration (active when the compressor is ON)
•
in replacement (active when the compressor is OFF)
It is possible:
•
deactivate the compressor under the threshold defined by
par. 559
•
deactivate the resistance over the threshold defined by
par.564
5.17 ELECTRIC HEATERS - performed by the customer
BT 7
13
14
40
39
XC2
0-10V
0V
R4
XC2 main control module terminal block
R4 modulating suplementary heaters (Customer supplied)
BT7 output temperature probe of the heater (Customer
supplied)
Text
559
564
OFF
OFF
Compr.
Res.
Configuration paramenters *
18
Enabling of aux. heater : 0 = NO; 1 = DHW;
2 = only system
559
OUTSIDE temp. limit at the compressor operating
560
Time measured by the start-up where the heater is not
activated
564
OUTSIDE temp. limit at the auxiliary operating
*
Parameters accessible through the installer password 115).
The access by pwd is reserved to qualified personnel;
The parameters changes may cause malfunctions.