60
WSAN-XIN 21-141
M0R940E13-00
13.3 Sound levels
Size
Sound power level
Sound pres-
sure level
Sound power
level
Octave band (Hz)
63
125
250
500
1000
2000
4000
8000
dB(A)
dB(A)
21
73
73
70
65
63
59
51
36
49
64
31
76
70
65
60
58
53
46
48
49
64
41
76
71
66
61
59
54
47
49
49
64
51
76
71
69
66
63
58
50
39
53
68
71
77
71
69
67
63
59
50
40
54
69
81
83
77
69
61
63
67
60
61
56
72
91
84
79
70
62
64
67
60
61
56
72
101
86
81
72
62
65
67
60
61
57
73
121
81
73
67
61
63
67
61
61
55
71
131
85
76
70
61
64
67
61
61
56
72
141
86
79
72
63
65
68
61
62
57
73
Sound levels refer to units with full load under nominal test conditions.
The sound pressure level refers to a distance of 1m from the outer surface of the unit operating in an open field.
Noise levels are determined using the tensiometric method (UNI EN ISO 9614-2)
Data referred to the following conditions:
utility side exchanger water inlet/outlet 12/7°C
source side exchanger water inlet/outlet 30/35℃
13.4 Admissible water flow rates
Min. (Qmin) and max. (Qmax) water flow-rates admissibles for the correct unit operation.
Size
21
31
41
51
71
81
91
101
121
131
141
Minimum flow
[l/s]
0,15
0,18
0,18
0,23
0,34
0,32
0,32
0,32
0,45
0,45
0,45
Maximum flow-rate
[l/s]
0,90
0,90
0,90
1,10
1,50
1,70
1,70
1,70
1,90
1,90
1,90
13.5 Unit without hydronic system
Exchanger pressure drop limit. Warning: don’t
use over this limit.
unit without hydronic assembly
Dp = pressure drop
Q = water flow
Exchamger pressure drop limit. Warning: don’t
use below this limit.
Содержание WSAN-XIN 21-141
Страница 4: ...4 WSAN XIN 21 141 M0R940E13 00...
Страница 44: ...44 WSAN XIN 21 141 M0R940E13 00 9 13 Spare parts sizes 21 31 41...
Страница 46: ...46 WSAN XIN 21 141 M0R940E13 00 9 14 Spare parts sizes 51 71...
Страница 48: ...48 WSAN XIN 21 141 M0R940E13 00 9 15 Spare parts sizes 81 101...
Страница 50: ...50 WSAN XIN 21 141 M0R940E13 00 9 16 Spare parts sizes 121 141...
Страница 70: ...70 WSAN XIN 21 141 M0R940E13 00...
Страница 71: ...71 Page intentionally left blank...