7.9 Remote controls
Check that the remote controls (ON-OFF etc) are connected and, if necessary, enabled with the respective parameters as indicated in the
“electrical connections” section.
Check that probes and optional components are connected and enabled with the respective parameters (“electrical connections” section and
following pages).
7.10 Water set point compensation with external temperature
It is possible to automatically change the set-point according to the outside temperature.
Enable the function:
Par: dS00 set-point compensation of the outside temp.
0 = Disabled
1 = Proportional
2 = Fixed (by step)
Cooling
With low ext. temperature the refrigerant requirements are reduced.
The internal comfort can also be obtained with a set-point higher than standard.
Example:
dS01 = - 6°C
dS03 = 4°C
dS05 = 36°C
setpoint = 10°C
compensated setpoint = 14°C
Parameter modification
Main menu
→
Parameters
→
dS
→
dS00
Cool Description
dS01
Temperature controller dynamic differential proportional band in Cool
dS03
Maximum temperature controller dynamic differential in Cool
dS05
Temperature controller dynamic differential setpoint in Cool
Содержание WSAN-XIN 21-141
Страница 4: ...4 WSAN XIN 21 141 M0R940E13 00...
Страница 44: ...44 WSAN XIN 21 141 M0R940E13 00 9 13 Spare parts sizes 21 31 41...
Страница 46: ...46 WSAN XIN 21 141 M0R940E13 00 9 14 Spare parts sizes 51 71...
Страница 48: ...48 WSAN XIN 21 141 M0R940E13 00 9 15 Spare parts sizes 81 101...
Страница 50: ...50 WSAN XIN 21 141 M0R940E13 00 9 16 Spare parts sizes 121 141...
Страница 70: ...70 WSAN XIN 21 141 M0R940E13 00...
Страница 71: ...71 Page intentionally left blank...