7 Start-up
7.1 General description
The indicated operations should be done by qualified technician with specific training on the product.
Upon request, the service centres performing the start-up.
The electrical, water connections and the other system works are by the installer.
Agree upon in advance the star-up data with the service centre.
Before checking, please verify the following:
•
the unit should be installed properly and in conformity with this manual
•
the electrical power supply line should be sectioned at the beginning
•
the line sectionalizing device is open, locked and equipped with the suitable warning
•
make sure no tension is present
7.2 Preliminary checks
For details refer to the different manual sections.
Unit OFF power supply
1. safety access
2. functional spaces
3. air flow: correct return and supply (no bypass, no stratification)
4. structure integrity
5. fans run freely
6. unit on vibration isolators
7. unit input water shut-off valves for cleaning
8. vibration isolators on water connections
9. expansion tank (indicative volume = 5% system content)
10. cleaned system
11. loaded possibile glicole so corrosion inhibitor
12. under pressure system
13. vented system
14. refrigerant circuit visual check
15. earthing connection
16. power supply features
17. electrical connections provided by the customer
7.3 Start-up sequence
For details refer to the different manual sections.
Unit ON power supply
1. compressor carter resistances operating at least since 8 hours
2. off-load voltage measure
3. phase sequence check (unit only 400/3/50)
4. unit ON
5. load voltage measure and absorptions
6. check of all fan operating
7. measure of return and supply water temperature and flow valutation
8. super-heating and sub-cooling measure and discharge temperature
9. check no anomalous vibrations are present
10. climatic curve personalization
11. set date and time
12. personalise scheduling
13. personalise DHW *
14. climatic curve personalization
15. set ambient keypad *
16. complete and available unit documentation
*If present
Содержание WSAN-XIN 21-141
Страница 4: ...4 WSAN XIN 21 141 M0R940E13 00...
Страница 44: ...44 WSAN XIN 21 141 M0R940E13 00 9 13 Spare parts sizes 21 31 41...
Страница 46: ...46 WSAN XIN 21 141 M0R940E13 00 9 14 Spare parts sizes 51 71...
Страница 48: ...48 WSAN XIN 21 141 M0R940E13 00 9 15 Spare parts sizes 81 101...
Страница 50: ...50 WSAN XIN 21 141 M0R940E13 00 9 16 Spare parts sizes 121 141...
Страница 70: ...70 WSAN XIN 21 141 M0R940E13 00...
Страница 71: ...71 Page intentionally left blank...