4.3 Condensate water
When a heat pump is running it produces a considerable amount of water due to the defrosting cycles of the external coil.
The condensation must be eliminated in a manner to avoid wetting pedestrian areas.
The unit anti-freeze electric resistance prevents the ice from forming inside the tray.
With extensive very cold outdoor temperatures, condensation could freeze outside the unit blocking the flow and causing a slow build-up of
ice; therefore special attention must be paid to eliminating condensation, raising the unit off the ground and evaluating whether antifreeze
elements should be installed.
A. Condensation collection basin
B. Unit support
C. Condensate discharge connection Ø 13