26 WSA-XEE
122-402
M02S40N16-00
If there are more units connected in a local network set the mode of operation.
MODE A
Every unit manages its own compressors according to the
setpoint.
Every unit optimizes its refrigeration circuits.
Pumps always active, even with compressor stoped.
P0343 = 0
P0344 > 0 °C
setpoint1 > setpoint2 > setpoint3
or
setpoint1 < setpoint2 < setpoint3
MODE B
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Pumps always active, even with compressor stoped.
P0343 = 1
P0344 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: optimal H2O temperature control
MODE C
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Active pumps only with active compressors.
P0343 = 2
P0344 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: minimum pumps consumption need balanced system (t1 = t2 = t3)
Path: Main Menu / Unit parameters / Master Slave
Parameters
Short description
Description
P0340:
Address unit
ProcessBus address unit
P0341:
Unit network
Number of network-connected units including the master
P0342:
Standby unit
Number of units kept in standby
P0343:
TypeRegMS
Operation mode: 0=mode A; 1=mode B; 2=mode C
P0344:
Offset Trm MS
Temperature Offset the master sum or subtract, depending on the way you set, in order of priority, to the set point of
the slave
Содержание WSA-XEE 182
Страница 8: ...8 WSA XEE 122 402 M02S40N16 00 2 4 Removable fan section for shipping...
Страница 15: ...M02S40N16 00 WSA XEE 122 402 15 5 6 Connections performer by customer Q 6...
Страница 58: ...58 WSA XEE 122 402 M02S40N16 00 Page intentionally left blank...
Страница 59: ...M02S40N16 00 WSA XEE 122 402 59 Page intentionally left blank...