32 WSA-XEE
122-402
M02S40N16-00
code
detailed description
t.i.
module
input
t.a.
eE001
Phase monitor
DI
687 central
T13 DL1
A/M
EE003
Pump 1 overload
DI
687 central
T13 DL2
M
EE004
Pump 2 overload
DI
687 central
T4 D1
M
EE005
Pump 3 overload
DI
687 central
T13 DL2
M
ee010
Master Offline - Master Slave network enabled
A
ee011
Unit 2 in alarm - Master Slave network enabled
A
ee012
Unit 2 OffLine - Master Slave network enabled
A
ee013
Unit 3 in alarm - Master Slave network enabled
A
ee014
Unit 3 OffLine - Master Slave network enabled
A
ee015
Unit 4 in alarm - Master Slave network enabled
A
ee016
Unit 4 OffLine - Master Slave network enabled
A
ee017
Unit 5 in alarm - Master Slave network enabled
A
ee018
Unit 5 OffLine - Master Slave network enabled
A
ee019
Unit 6 in alarm - Master Slave network enabled
A
ee020
Unit 6 OffLine - Master Slave network enabled
A
ee021
Unit 7 in alarm - Master Slave network enabled
A
ee022
Unit 7 OffLine - Master Slave network enabled
A
EE023
Pump 1 thermal protection
DI
965 hydronic
T1 X4
M
EE024
Pump 2 thermal protection
DI
965 hydronic
T1 X5
M
EE025
Pump 3 thermal protection
DI
965 hydronic
T1 X6
A
EE026
Inverter thermal protection
DI
965 hydronic
T5 DL1
A
ee027
Water inlet temperature probe faulty
AI
687 central
T1 B1
A
ee028
Water outlet temperature probe faulty
AI
687 central
T1 B2
A
ee029
External air temperature probe faulty
AI
687 central
T1 B3
A
ee030
Signal logoff or short circuit
AI
687 central
T2 X1
A
ee031
Signal logoff or short circuit
AI
687 central
T2 X2
A
ee032:
External Humidity probe faulty
AI
687 central
T2 X3
A
ee033:
Cabinet temperature probe faulty
AI
687 central
T2 X4
A
ee034:
Hydronic module on the ProcessBus is disconnected
periperal bus
A
ee035:
Cool opening valve: error limit
DI
945 4P
X2
A
ee036:
Heat opening valve: error limit
DI
945 4P
X4
A
ee037:
Cool closing valve: error limit
DI
945 4P
X1
A
ee038:
Heat closing valve: error limit
DI
945 4P
X3
A
ee039:
Communication timeout 4P module
Logico
945 4P
periperal bus
A
ee040:
FCI module water temperature probe fault
AI
955 FCI
X1
A
ee041:
Communication timeout FCI module
Logico
955 FCI
periperal bus
A
EE044:
FCI module P1 thermal protection
DI
955 FCI
X5
M
EE045:
FCI module P2 thermal protection
DI
955 FCI
X6
M
EE046:
FCI module P3 thermal protection
DI
955 FCI
X7
M
ee050:
User side exchanger, differential pressure probe fault
965 hydronic
X3
A
ee054:
Recovery pump thermal protection
DI
955 FCI
X6
A
ee101:
Circuit 1 module on the ProcessBus is disconnected
periperal bus
A
ee102:
Driver 1 module on the ProcessBus is disconnected
periperal bus
A
ee103:
Recovery 1 module on the ProcessBus is disconnected
periperal bus
A
ee104:
Driver 1 blocked
94U driver
A
EE106:
Compressor 1 thermal protection
DI
985 circuit 1
T4 D1
M
EE107:
Compressor 2 thermal protection
DI
985 circuit 1
T4 D2
M
EE108:
Compressor 3 thermal protection
DI
985 circuit 1
T4 D3
M
EE118:
Source side protection
DI
985 circuit 1
T9 DL2
M
ee122:
Faulty probe - discharge temperature compressor 1
AI
985 circuit 1
T1 B1
A
ee123:
Faulty probe - discharge temperature compressor 2
AI
985 circuit 1
T1 B2
A
ee124:
Faulty probe - discharge temperature compressor 3
AI
985 circuit 1
T2 X2
A
ee125:
Faulty probe - source 1 temperature
AI
985 circuit 1
T1 B3
A
Содержание WSA-XEE 182
Страница 8: ...8 WSA XEE 122 402 M02S40N16 00 2 4 Removable fan section for shipping...
Страница 15: ...M02S40N16 00 WSA XEE 122 402 15 5 6 Connections performer by customer Q 6...
Страница 58: ...58 WSA XEE 122 402 M02S40N16 00 Page intentionally left blank...
Страница 59: ...M02S40N16 00 WSA XEE 122 402 59 Page intentionally left blank...