M02S40N16-00
WSA-XEE
122-402
29
7.4 Change unit state
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press
2
Main menu
Select
Cmd Local state
3
Set
OFF - ECO - ON - Pump On
*
4
Confirm
6
Exit
* Local state
ECO: recurrent pump ON-OFF; compressors keep water system at setpoint ECO
Pmp ON: pump ON, compressor OFF
7.5 Change the mode
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press
2
Main menu
Select
Cmd Local mode
3
Set
Cool: water cooling
Heat: water heating (option)
4
Confirm
5
Exit
7.6 Modify
setpoint
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press
2
Main menu
Select
Unit parameters
3
Unit parameters
Confirm
Set Point
4
Select
Set Point
5
Set
Set Point
6
Confirm
7
Exit
Parameters
Short description
Description
P0001
SetPoint Cool
Setpoint Cool
P0002
SetPoint Heat
Setpoint Heat
Not used
P0003
2°SetPoint Cool
2° Setpoint Cool
Enable by remote switch
P0004
2°SetPoint Heat
2° Setpoint Heat
not used currently
P0005
SetPoint ECOCool
Economic summer SetPoint
P0006
SetPoint ECOHeat
Economic winter SetPoint
Not used
P0007
SetPointRec
Recovery Set Point
Содержание WSA-XEE 182
Страница 8: ...8 WSA XEE 122 402 M02S40N16 00 2 4 Removable fan section for shipping...
Страница 15: ...M02S40N16 00 WSA XEE 122 402 15 5 6 Connections performer by customer Q 6...
Страница 58: ...58 WSA XEE 122 402 M02S40N16 00 Page intentionally left blank...
Страница 59: ...M02S40N16 00 WSA XEE 122 402 59 Page intentionally left blank...