22
1.1
INTRODUCTION
The cast iron boilers
“GG GMP - GHP
2S”
for gas-oil or gas has been designed
in compliance with the European Directi-
ves 2009/142/CEE, 2004/108/CEE,
2006/95/CEE, 92/42/CEE.
The components for
“GG GMP - GHP
2S”
installation are supplied in three
separate packages: boiler body with
smoke chamber dismantled and inser-
ted in the combustion chamber, casing
with enclosed documents and control
panel.
Instead, the boilers
“GG GHP 6÷15
2S (S)”
are supplied with the disman-
tled boiler body.
1
BOILER DESCRIPTION
1.3
TECHNICAL FEATURES
1.3.1
“GG GMP 2S” boiler
560 (GMP) - 700 (GHP)
1
030 (GMP) - 1
235 (GHP)
P
125 (GMP)
135 (GHP)
ø 1
50 (GMP)
ø 200 (GHP)
2
70 (GMP)
330 (GHP)
70 (GMP)
85 (GHP)
695 (GMP) - 8
75 (GHP)
865 (GMP) - 1
0
75 (GHP)
M
R
S
1.2
DIMENSIONAL DETAILS
Fig. 1
GG GMP 2S
GG GHP 2S
M C.H. flow
1
1/
2
”
2”
R C.H. return
1
1/
2
”
2”
S
Boiler/filling drain
3/4”
3/4”
6
7
8
9
10
Output
kW
58.9
68.0
77.2
86.4
95.7
Input
kW
65.0
75.0
85.0
95.0
105.0
Class efficiency (CE 92/42 directive)
P (depth)
mm
595
670
750
825
900
Sections
n°
6
7
8
9
10
Maximum water head
bar
4
4
4
4
4
Water content
l
37.5
42.0
46.5
51.0
55.5
Loss of head smoke
mbar
0.20
0.16*
0.22*
0.30*
0.35*
Comb. chamber pressure
mbar
– 0.01
0.06
0.08
0.08
0.10
Suggested chimney depression
mbar
0.21
0.22
0.30
0.38
0.32
Smokes temperature
°C
208
205
198
195
192
Smokes flow
m
3
n/h
75.0
87.9
100.4
113.1
118.8
Adjustment range Heating
°C
30÷85
30÷85
30÷85
30÷85
30÷85
CO
2
%
12.9
12.7
12.6
12.5
12.7
Weight
kg
261
293
325
357
389
* Without baffles